PROGRAMMING (continued) 

 

9A. LAST TRIPPED INFORMATION 

This information is held in memory even if power is removed.  

 
This feature allows the user to view and recall the key information relating to the last trip event and it can store up to 10 trip events. It is accessed as described in Section 8 
on the previous page.  
 
The information displayed highlights the cause of the trip (i.e. which phase for example), the level of current at the time the trip occurred; the triggering method (Low-set 
or High-set) and which relays were activated. It also shows the elapsed time from powering the 

P9690

P9690

P9690

P9690

 to the trip occurring and displayed against “Ttrip” as well as showing 

the time difference between the trip displayed and the one previous to that. This is shown against “Tdiff”. 
 
An example of the screen layout is shown below. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

If there is only one trip event stored in the memory, the display will show “Tdiff: ----d--h--m--s” when viewed.

 

Phase which 
caused the trip 
to occur 
(i.e. L2) 
 
 
Level of current 
on other inputs 
at time of trip 

Trip number 
(1…10) 

 
 

Relays that were 
activated at trip 

IL1        20.70A      I>>  

   1

 

IL2       

89.00A     

R1    R2

 

IL3        27.50A     
Io          0.00A        
 

Ttrip: 0000d00h00m00s 
Tdiff: 0000d00h00m00s 

 

Level which was 
triggered (i.e. High-set) 

9B. RECALLING THE LAST TRIPPED INFORMATION 

If the unit has logged the maximum number of trips which can be stored, then the display will show “Tdiff: ----d--h--m--s” when trip screen 10 is viewed. 

The screen will revert back to Normal operation after 1 minute if no further button presses are made. 

If a trip condition occurs whilst in this mode, the screen will automatically change to display the information relating to the current status.

 

 

 

As described in Section 8, use the 

to gain access to the Last Tripped Information screen. The display will show the most recent trip information as follows:

 

 
 
 
 
 
 

 

If more than one trip event is stored, use the 

 and 

buttons to select the screens accordingly.

 

 
 
 
 

 
 

 

 

 

Press the 

button to exit the screen information when finished or allow to time out automatically.

 

 

IL1

 

    

1.65A

 

    I>     

 1

 

IL2      

15.00A     

R1    R2

 

IL3       8.40A        
Io        0.00A       
 

Ttrip: 0001d13h15m04s 
Tdiff: - - - -d - -h - -m - -s 

 

IL1

 

    

1.65A

 

    I>     

 1

 

IL2      

15.00A     

R1    R2

 

IL3       8.40A        
Io        0.00A       
 

Ttrip: 0001d19h24m56s 
Tdiff: 0000d06h09m52s 

 

IL1

 

    

1.80A

 

    I>     

 2

 

IL2      

21.35A     

R1    R2

 

IL3       9.20A        
Io        0.00A       
 

Ttrip: 0001d13h15m04s 
Tdiff: - - - -d - -h - -m - -s 

 

 

 

Ttrip: 
The elapsed time from 
applying power to the 
current trip 

Tdiff: 
The time difference 
between the current trip 
and the previous trip 

The example on the left shows the problem on phase L2 on 
both trip events. The difference between the first recorded 
trip and second was 6h 09m

6h 09m

6h 09m

6h 09m and 52s

52s

52s

52s. 

9C. CLEARING THE LAST TRIPPED INFORMATION HISTORY 

Once the information has been deleted, it will not be possible to recall this. 

“Ttrip” information is still retained but won’t be displayed after the carrying out this 

operation (See 9D) 

 

 

Press the 

button to access the relevant screen.

 

 

Press the 

 and 

buttons simultaneously to delete the information. 

When this is complete, the screen will show:

 

 
 
 
 

 
 

 

Press the 

button again to exit.

 

 
 

 
 
 

No previous trip info

 

 

9D. CLEARING “Ttrip” INFORMATION 

If the tripping history hasn’t been deleted, previous information will be displayed 

from the last time the unit was powered up. 

 

 

The “Ttrip” information will still be held in memory after deleting the trip 
history is made and also if power is removed and re-applied. However, 
when power is re-applied, the internal counter will reset and start from zero

 

 

Only when a new trip condition occurs will the “Ttrip” information get 
updated and be displayed on the most recent screen.

 

 
 
 
 

 
 

 

 
 
 
 

Содержание P9690

Страница 1: ...o or Manual resetting Relay 2 has the added option of being allowed to energise at the start or end of a time out period If assigned to energise at the start the Relay can be used to operate a buzzer...

Страница 2: ...ccurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9690 P9690 P9690...

Страница 3: ...TING Default setting for Relay 2 is linked to O C E F and energising at the end of the time out period Resetting mode is Auto Setting of Relay 2 is carried out in a similar manner as Relay 1 however i...

Страница 4: ...urther button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8 u...

Страница 5: ...IO 0 00A Phase with fault 2 EARTH FAULT When an Earth fault occurs causing a flow in current through the Neutral an increase in current reading on the LCD will occur When the level of current exceeds...

Страница 6: ...tor for each phase 4 HOURS RUN This will run for as long as power is applied to the relay The displayed time cannot be reset The displayed time will be retained in memory during removal of power to th...

Страница 7: ...0 01 t t t t s s s s Normal Inverse Normal Inverse Normal Inverse Normal Inverse 3 10 3 10 3 10 3 10 NI NI NI NI 3 10 3 10 3 10 3 10 t t t t s s s s k k k k 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 0...

Страница 8: ...CHNICAL SPECIFICATION Aux Supply voltage Un 1 2 85 265VAC 85 370VDC1 18 55VAC 18 72VDC Voltage range should be specified at time of ordering Rated frequency 50 60Hz AC Supplies Isolation Over voltage...

Отзывы: