57
X-VA-MT3809G-MT3810G-eng/541B182AAG/A/2022-10
Brooks Instrument
Installation Manual MT3809G & MT3810G
Section 3 Operation
For details on the Foundation Fieldbus interface, refer to the supplemental
manual (X-DPT-FF-MT3809G-Alarms-eng), also available on
BrooksInstrument.com/Documentation
Communication with Transmitter using Local Operator Interface with LCD Display
The LCD display is a three line liquid crystal display. It can easily be
SURJUDPPHGWRSURYLGHEDVLFLQIRUPDWLRQVXFKDVÀRZUDWHVDQGSURGXFW
WRWDOL]DWLRQ&RQ¿JXUDWLRQDGMXVWPHQWVWRXSSHUORZHUUDQJHYDOXHV
can also be performed using the display. Access to the display can be
accomplished by removing the cover or by using the supplied magnet with
the cover in place. Refer to Figure 3-4 for the menu tree for more details.
$GMXVWLQJ,QGXFWLYH$ODUPVRUVZLWFKHV
To modify the alarm set points, remove the front cover with gasket of the
indicator housing by removing the four screws.
Set the alarm position by loosening the two pointer screws, moving the
pointer to the desired alarm setting and tightening the screws.
Replace the indicator housing cover with gasket and secure with the four
screws.
Simulate
Foundation Fieldbus specs require that the customer be able to access
and enable/disable physical "simulate", this can be done by creating a
short between Pin 9 and Pin 7 on the terminal strip. See Figure 3-3 below.
)LJXUH7UDQVPLWWHU6LPXODWH&RQQHFWLRQ
Communication with F
OUNDATION
Fieldbus Transmitter