![Brooks 5851E Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/brooks/5851e/5851e_installation-and-operation-manual_2818749017.webp)
2-7
Brooks
®
Model 5851E
Section 2 Installation
Installation and Operation Manual
X-TMF-5851E-MFC-eng
Part Number: 541B104AAG
November, 2008
Figure 2-3 Model 5851E Card Edge Connector Hookup Diagram
Figure 2-4. D-Connector Pin Arrangement.
PIN NO.
FUNCTION
COLOR CODE
1
Cmd. Common (Command Pot "CCW")
Black
2
0-5 Volt Signal Output
White
3
N/C
Red
4
Valve Off
Green
5
+15 Vdc Supply
Orange
6
-15 Vdc Supply
Blue
7
Valve Test Point
Wht/Blk
8
Cmd. Input or Cmd. Pot "S"
Red/Blk
9
Supply Voltage Common
Grn/Blk
10
0-5 Volt Signal Common
Org/Blk
11
+5 Volt Reference Output (Command Pot "CW")
Blu/Blk
12
Valve Override
Blk/Wht
13
Not Used
Red/Wht
14
Chassis Ground
Grn/Wht
15
Remote Transducer Input*
Blu/Wht
*Jumper Selectable
Notes:
1. Cable shield tied to chassis ground
in meter connector. Make no
connection on customer end.
2. All power leads must be connected
to power supply.
1
15
9
8