Bronkhorst®
Instruction Manual mini CORI-FLOW ML120
9.17.097G
34
Setpoint
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…32000
9
1/1
0x0021/34
This parameter is used to set the required flow rate for the controller. The signals have the same range as
Measure
, but the
setpoint range is limited between 0 and 100% (0…32000).
Actual Density
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Float
R
-3.4E+38…
3.4E+38
270
116/15
0xF478…0xF479/62585…62586
This parameter returns the actual density that is measured by the instrument.
Advanced
Fmeasure
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Float
R
-3.4E+38…
3.4E+38
205
33/0
0xA100…0xA101/ 41217…41218
Floating point variant of
Measure
.
Fmeasure
shows the measured value in the capacity and capacity unit for which the
instrument has been set.
Fmeasure
is dependent of
Capacity Unit
and
Sensor Type
.
Fsetpoint
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Float
RW
0…3.4E+38
206
33/3
0xA119…0xA11A/ 41241…41242
Floating point variant of
Setpoint
.
Fsetpoint
shows the setpoint in the capacity and capacity unit for which the instrument
has been set.
Fsetpoint
is dependent of
Capacity Unit
and
Sensor Type
.
Setpoint Slope
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…30000
10
1/2
0x0022/35
The value of this parameter represents the time it would take to adjust the setpoint if it were changed from 0 to 100%. This
feature can be used to smooth 'nervous' controller behavior, e.g. to reduce setpoint overshoot or undershoot.
The supported range corresponds with 0…3000 seconds. Default value = 0.
Example:
If
Setpoint Slope
= 100 it will take 10 seconds to adjust the setpoint if it is changed from 0 to 100%. A setpoint change of 20%
will take (20%/100%)*10 seconds = 2 seconds.
Analog Input
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
R
0…65535
11
1/3
0x0023/36
This parameter contains a digital translation of the analog input signal (if applicable).