Pure induct
GB
2.1 Specifications Pure induct
2. Technical specifications
Article code
351000
Recommended air flow
<600 m
3
/h
Power
14 W
Efficiency
99 %
Size
780 x 374 x 340 mm
(excl. connection pieces, 50 x Ø200 mm)
Connection diameter
Ø200 mm flange
Weight
12 kg
Materials
Galvanized steel
Standard collectors
2 Collectors
Air cleaning technique
ASPRA (optional Active Carbon)
Power input
~110-240 VAC/ 50 - 60 Hz
Colours
White
Installation
Mounted on walls or above ceiling and connected
to ventilation shafts
Operation conditions
Indoors in a ventilated area under temperature
conditions of 0 to 50 °C with a relative humidity of
0 to 90%.
Control
Manual (on/off)
Including
3 Flange clamps, 1 Pure induct collector box, Pure
induct collector, 2 connection pieces
Excluding
(necessary for mounting)
2 Mounting brackets, 2x mounting material,
connection pieces (for connection to duct)
Extra collectors [E] and replacements [R]
Article code
Pure induct collector [R]
351002
Pure induct ACF [E]
351003