35-DVRS31NB(N)-2
16
Installation Instructions Cont.
The horizontal run must have a
1/4”
rise on an exterior wall and
must meet all local and national building codes, and must not be
easily blocked or obstructed. Termination clearances are as follows
(see Figure 16):
A.
Clearance above ground, verandah, porch, deck, or balcony:
12”
minimum (30 cm.)
B.
Clearance to a window or door that may be opened:
9”
mini-
mum (23 cm)
C.
Vertical clearance to a ventilated soffit located above the termi-
nation within a horizontal distance of 2 feet from the centerline
of the termination:
18”
minimum (46 cm).
Note: Clearances
are to be in accordance with local installation codes and
the requirements of the gas supplier.
D.
Clearance to an unventilated soffit:
12”
minimum (30 cm).
Note: Clearances are to be in accordance with local instal-
lation codes and the requirements of the gas supplier.
E.
Clearance to an outside corner:
9” (23
cm).
Note: Clearances
are to be in accordance with local installation codes and
the requirements of the gas supplier.
F.
Clearance to an inside corner:
9” (23
cm).
Note: Clearances
are to be in accordance with local installation codes and
the requirements of the gas supplier.
G.
Do not install above a meter/regulator assembly within 3 feet
(90 cm) horizontally from the centerline of the meter/regulator.
Note: Clearances are to be in accordance with local instal-
lation codes and the requirements of the gas supplier.
H.
Clearance to a service regulator vent outlet:
6’
minimum (1.8
m)
I.
Clearance to a non
-
mechanical air supply inlet to a building or
the combustion air inlet to any other appliance:
12”
minimum
(30 cm)
J.
Clearance to a mechanical air supply inlet:
6’
minimum (1.8 m)
K.
Clearance above paved sidewalk or paved driveway located on
public property: refer to local code
L.
Clearance under open verandah, porch, deck, or balcony:
12”
minimum (30 cm).
Note: Clearances are to be in accordance
with local installation codes and the requirements of the
gas supplier.
M.
Maximum horizontal run
5’
after
2’
vertical rise. Liquid Propane
gas
5’
horizontal run to
35’
vertical rise. Natural Gas maximum
35’
horizontal run with
7’
vertical rise.
Note: Clearances are to
be in accordance with local installation codes and the re-
quirements of the gas supplier.
Vent Termination Locations
Fig 16
-
A
Horizontal Installation