D521-Manual_EN_Rev07 2017_05_26
Page 9 of 31
Param.
No.
Default
value
Parameter Function
P05.xx
Alarm SP2
P05.00 01200 Setpoint (by same terms as programmed in P01.03)
.01
05.0
Hysteresis bandwidth for SP: 00.1….99.9 % of setpoint
.02
1 Hysteresis location: 0 : above / 1 : below
.03
0 Relay state at ' n > SP ': see table of parameter description
.04
0 Starter function effective for setpoint SP2: 0 : no / 1 : yes
.05
0 Alarm state during starter phase: 0 : ' n < SP ' / 1 : ' n > SP '
.06
0 Alarm state at sensor fault: 0 : acc. to variable / 1 : ' n < SP ' / 2 : ' n > SP '
P06.xx
Alarm SP3
P06.00 01300 Setpoint (by same terms as programmed in P01.03)
.01
05.0
Hysteresis bandwidth for SP: 00.1….99.9 % of setpoint
.02
1 Hysteresis location: 0 : above / 1 : below
.03
0 Relay state at ' n > SP ': see table of parameter description
.04
0 Starter function effective for setpoint SP3: 0 : no / 1 : yes
.05
0 Alarm state during starter phase: 0 : ' n < SP ' / 1 : ' n > SP '
.06
0 Alarm state at sensor fault: 0 : acc. to variable / 1 : ' n < SP ' / 2 : ' n > SP '
P07.xx
Alarm SP4
P07.00 01400 Setpoint (by same terms as programmed in P01.03)
.01
05.0
Hysteresis bandwidth for SP: 00.1….99.9 % of setpoint
.02
1 Hysteresis location: 0 : above / 1 : below
.03
0 Relay state at ' n > SP ': see table of parameter description
.04
0 Starter function effective for alarm SP4: 0 : no / 1 : yes
.05
0 Alarm state during starter phase: 0 : ' n < SP ' / 1 : ' n > SP '
.06
0 Alarm state at sensor fault: 0 : acc. to variable / 1 : ' n < SP ' / 2 : ' n > SP '
P08.xx
Data interface
P08.00
3 Baudrate: 0 : 300 / 1 : 1200 / 2 : 9600 / 3 : 19200 / 4 : 38400
.01
001
Device no.: 001 …125
4.2
Setting the Parameters via RS232-Interface
Only possible for OEM with special interface software IS-RS232-S and adapter cable L3D01
from BRAUN.
PC must have a 9pole SUB-D RS232 Interface.