Parameter Group P01.xx (continued)
Measurement Configuration, Sensor Monitoring
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P01.07
Reserved for future applications
P01.08
Sensor monitoring on/off
Range: 0 .. 2
If the sensor is monitored, the fault alarm may be latched until it is reset.
Setting:
0 : off (sensor monitor disabled)
1 : on
2 : on, latched
Note:
If P01.08 set to 0, Step P01.09 is meaningless.
P01.09
Mode of sensor monitoring
Range: 0 .. 5
Setting:
0 : Without monitoring
1 : Checks sensor current drain
2 : Checks signal voltage level volt sensor at stand still
3 : Current drain and voltage level
4 : Checks signal voltage level inductive sensor at stand still
5 : Checks signal voltage level NAMUR sensor at stand still
Note:
- Selection of Setting 0 makes Step P01.08 meaningless.
- The voltage level check is only possible with Braun sensor type A5S...
In this instance a signal lead break between sensor and D521 will be
detected at stand still of the machine. This check requires a jumper
between terminals 14 and 16. Maximum admissible signal voltage is
30Vdc.
- For Ex Applications with SIL2 requirements (with A5S1.. and D461)
P01.09 must be set to 2.
- For Non-Ex Applications with SIL2 requirements (with A5S0)
P01.09 must be set to 3.
P01.10
Fix value 001