D521-Manual_EN_Rev07 2017_05_26
Page 8 of 31
4
Parameters
4.1
Summary of parameters and their default values as set on delivery
Param.
No.
Default
value
Parameter Function
P00.xx
Code figure, Parameter Lock, Front side Reset of Alarms
P00.00
0000 Code figure
.01
0000 New code figure
.02
0 Front side Parameter Lock : 0: locked / 1: enabled
.03
0000 Minimum Measuring Period (in xxxx milliseconds)
.04
000 Starter Time Period (in xxx sec)
P01.xx
Input Scaling
P01.00
0 Decimals of input frequency
.01 00100 Value of nominal input frequency in Hz
.02
0 Decimals of speed value
.03 00100 Nominal speed (e.g. in RPM)
.04 00001 Lower limit of the speed range
.05
0 Hysteresis of input response level (0 : A5S sensor, 1 : MPU or NAMUR sensor)
.06
1 Reserved for future applications
.07
0 Reserved for future applications
.08
1 Sensor monitoring: 0: off / 1: on / 2: on, latched
.09
1 Mode of sensor monitoring: 0: none / 1: current / 2: voltage / 3: both / 4 : inductive / 5 : NAMUR
.10
001 Fix value 001
P02.xx
Display
P02.00
0 LSDs on zero
.01
0.3 Updating sequence (in x.x seconds)
P03.xx
Analog Output
P03.00 10000 High-end speed value
.01 00000 Low-end speed value
.02
1 Zero level: 0 : dead zero / 1 : live zero
.03
1 Output mode: 0 : signal voltage / 1 : current
.04
0 Output level at sensor fault: 0: no change / 1: min / 2: max
.05
0 Output direction: 0/4..20 mamps (0/2..10 volts) / 1 : 20...4/0 mamps (10..0/2 volts)
P04.xx
Alarm SP1
P04.00
01100 Setpoint (by same terms as programmed in P01.03)
.01
05.0
Hysteresis bandwidth for SP: 00.1….99.9 % of setpoint
.02
1 Hysteresis location: 0 : above / 1 : below
.03
0 Relay state at ' n > SP ': see table of parameter description
.04
0 Starter function effective for setpoint SP1: 0 : no / 1 : yes
.05
0 Alarm state during starter phase: 0 : ' n < SP ' / 1 : ' n > SP '
.06
0 Alarm state at sensor fault: 0 : acc. to variable / 1 : ' n < SP ' / 2 : ' n > SP '
Continued on next page