Installer Option Descriptions 

continued

9. 

This thermostat includes an automatic compressor protection feature to 

  avoid potential damage to the compressor from short cycling. This    
  thermostat automatically provides an adjustable delay after turning off  
  the compressor. This protection is also present in the first stage heat mode 
  of operation on single stage heat pump systems to protect the compressor.

10.

 During the COOL mode of normal operation the fan will stay on for 60  

  seconds after the cooling system has satisfied the set point temperature  
  and has turned off the compressor. This allows the system to provide  
  higher efficiency during cooling operation.The delay is selectable between  
  0, 30, 60 or 90 seconds.

11.

 The Recirculating Fan Mode provides more even temperature distribution  

  and improves indoor air quality by circulating air through the furnace filtra- 
  tion system more often. The Recirculating Fan can be locked “on”, so that  
  the only fan selections available to the user are CIRC and ON. By locking  
  the Recirculating Fan to CI

r

CON, the user will only have the option to run  

  the fan all the time (ON) or use the Recirculating Fan Feature (CIRC). When  
  locked on, the fan circulates at a fixed time of 12 minutes on, 24 minutes off.  
  In the CIRC mode, the fan can be set to run every 24, 40, 60 or 120 minutes  
  (see chart below). The Recirculating Fan feature is available in the COOL, OFF,  
 

HEAT, or EMER mode. To set the fan run time, see page 12.

12.

 If a Braeburn

®

 indoor or outdoor remote sensor is connected during instal- 

  lation, the thermostat will automatically detect the type of sensor. When an  
  indoor sensor is detected, you may select between internal (sensI), external  
  (sensE), or averaging (sensA) of internal and external for temperature control.  
  When an outdoor sensor is automatically detected, the thermostat will remove  
  the choices for indoor sensing from the menu and enable outdoor measure- 
  ment. The outdoor sensor may be used to determine if balance points have  
 

been exceeded, and for outdoor temperature display. For proper auto-detection,  

  you must use a Braeburn brand external sensor. Should the external sensor  
  become unwired, the thermostat will retain the settings, but the balance points,  
  temperature dependent humidity control, and outdoor temperature display 
  will be disabled until the external sensor is repaired. Test the operation of the  
  external sensor by pressing the 

BACK

 and 

NEXT

 buttons at the same time. 

4

Programming Installer Settings 

cont.

Option Settings 

Temperature 

   

Control

sens I (Internal Thermostat Sensor)  At Thermostat 

sens E (Remote Indoor Sensor) 

At Remote Sensor

sens A (Internal and Remote) 

Average between

   

Internal and Remote

Fan Cycle   Fan Off Time   Fan Run Time

  Setting 

   (minutes) 

    (minutes) 

 

24

 

24  

12

  40

 

40 

12

  60

 

60 

12

  120

 

120 

 

12

7

4

Programming Installer Settings 

cont.

   

Factory  

Installer Options 

Default 

Options 

Comment

15

 Compressor 

balc   O 

balc   O, 

 

Scrolls between NO (no lockout) 

      Balance Point 

 

balc 1O,

 

and 10 to 50˚ F (-12 to 10˚ C) to

   

 

balc 5O

 

set Compressor Balance Point. 

   

 

 

Only available with multi-stage

   

 

 

heat pump and outdoor sensor

   

 

 

connected.

16

 Auxiliary Balance 

bala   O 

bala   O, 

Scrolls between NO (no lockout)

  Point 

 

bala  7O, 

and 70 to 40˚ F (21 to 4˚ C) to set

   

 

bala  4O  

Auxiliary Balance Point. Only available

   

 

 

with multi-stage heat pump and 

   

 

 

outdoor sensor connected.

17

 Heating Set Point 

hea  90 

hea  90, 

Scrolls between 90 and 60˚ F

  Upper Limit

 

 

hea  60 

(32 and 10˚ C).

18

 Cooling Set Point 

cool 45

 

cool 45,

 

Scrolls between 45 and 80˚ F

  Lower Limit 

 

cool 80

 

(7 and 27˚ C).

Installer Option Descriptions
1.

   Selects preferred temperature scale of either ºF or ºC.

2.

   Selects Auto Changeover on or off. When off is selected, the AUTO icon  

  will not be displayed when selecting the system options with the system  
  switch. When Auto Changeover mode is enabled and selected, the system  
  automatically switches between heating and cooling when the room   
  temperature meets the programmed heating or cooling set points. 

3.

   Selects single stage conventional (11C), 2 stage conventional (22C), single  

  stage heat pump (11HP), 2 stage heat pump (22HP), or 3 stage heat pump  
  (32HP). Any change made to the system type resets Installer Options 4  
  through 8 to their default values dependent on system selected.

4.

   Selects between 1st stage gas or electric heat Fan Control. This Installer  

  Option is not available with a heat pump system.

5.

   Selects aux-stage gas or electric heat Fan Control. This Installer Option is  

  only available with a 2 or 3 stage heat pump system.

6.

   For heat pump units with an electric auxiliary stage, both the first and  

  second stages of heating will run when a call for second stage heat is  
  made. For heat pump units with a fossil fuel auxiliary stage, the compressor  
  stage(s) will be locked out one minute after a second stage heat call, and  
  the second stage will only be used. 

NOTE: 

Can be overridden by Auxiliary  

  Balance Point. See Installer Option number 16 in the chart above for details.

7.

   Select between turning the AC power interrupt warning off or on. During  

  a power loss, the thermostat will display an outage warning (-AC). All set 
  tings will be maintained until the outage period is over. This Installer Option  
  is only available when thermostat is installed as a hardwired unit.

8.

   This thermostat provides cold weather compressor protection by locking  

  out the compressor stage (1st stage) of heating for a period of time after a  
  power outage greater than 60 minutes. The lockout period is one hour less  
  than the outage time, up to a maximum of 12 hours. During that period of  
  time, the auxiliary heat stage will still be available to maintain the set point  
  temperature. The compressor lockout can be disabled by setting this option  
  to OFF 

(continued on page 8)

.

Содержание Premier 3300

Страница 1: ...8 Troubleshooting 9 Wiring Diagrams 1 Specifications Electrical Rating 24 Volt AC 18 30 Volt AC 1 amp maximum load per terminal 5 amp maximum load all terminals Control Range 45º 90º F 7º C 32º C Accuracy 1º F 5º C 3 RH AC Power 18 30 Volt AC DC Power 3 0 Volt DC 2 AA Alkaline batteries included Compatibility Compatible with low voltage single stage or multi stage heat cool systems including heat ...

Страница 2: ...es in the sub base mark the placement of the mounting holes through the slots and onto the wall Ensure the wires come out of the wall into the center hole of the sub base 5 After verifying the drill will not damage items in the wall use a 3 16 drill to create the mounting holes Gently tap the supplied plastic anchors into the holes in the wall 6 Place the thermostat sub base against the wall in th...

Страница 3: ... deg No Limit Status After CLEAR Factory Default Settings At initial power up or after Installer CLEAR button is pressed the thermostat is reset to factory defaults Installer CLEAR button is located on the circuit board 3 3 Quick Reference Model 3300 shown with cover open SYSTEM Button Selects AUTO Heat Cool COOL OFF HEAT or EMER BACK Button Scrolls backwards between setup screens NEXT Button Scro...

Страница 4: ...ature display or balance point control is automatically detected Test outdoor sensor connection by pressing BACK and NEXT at the same time 13 Set Security Level sec 2 sec i Selects between level 1 or level 2 for Keypad Lock sec 2 keypad lockout 14 Dead Band a 3 a 2 Selects Auto Changeover Dead a 3 Band of 2 3 4 5 F 1 0 1 5 2 0 a 4 2 5 C Only available if Auto a 5 Changeover is enabled in option 2 ...

Страница 5: ...4 12 40 40 12 60 60 12 120 120 12 7 4 Programming Installer Settings cont Factory Installer Options Default Options Comment 15 Compressor balc O balc O Scrolls between NO no lockout Balance Point balc 1O and 10 to 50 F 12 to 10 C to balc 5O set Compressor Balance Point Only available with multi stage heat pump and outdoor sensor connected 16 Auxiliary Balance bala O bala O Scrolls between NO no lo...

Страница 6: ... button The and buttons can be pressed together to enter the lock code but the buttons do not work individually to adjust the temperature The lock security level is set in the Installer Options and the lock code is set in the User Options 14 When Auto Changeover mode is enabled and selected the system automatically switches between heating and cooling when the room temperature meets the normal cri...

Страница 7: ...digit code you have created Locking the Thermostat Press and hold the and buttons together for five seconds While you are holding these buttons the LOCK icon will flash once per second and after 5 seconds the LOCK icon and three digits will appear in the display Use the or buttons to enter the lock code you previously created see Setting Your Lock Code After entering the first digit press the NEXT...

Страница 8: ...ies to provide power for the thermostat if 24 volt AC power is not connected to the terminal block This thermostat is equipped with a unique three level low battery detection feature that constantly monitors the batteries during normal operating mode to determine whether they have sufficient power to provide proper operation When this feature determines that the battery status is low a low battery...

Страница 9: ...enough Potential Solution Increase or decrease temperature differential settings as ap propriate to provide the desired performance level See page 9 Symptom Low battery indicator is shown in thermostat display Potential Solution Replace batteries immediately to maintain proper system operation See page 14 Symptom Thermostat display is blank Potential Solution It is possible that AC power is not pr...

Страница 10: ... to enter unlock mode Press to enter the 3 digit unlock code Press the NEXT button to move to the next digit Symptom Fan continues to run all the time whether the system is on or off Potential Solution Check to make sure the fan control switch is in the AUTO posi tion This will allow the fan to run only when the heating or cooling system is turned on and running Check thermostat wiring to make sur...

Страница 11: ... other 2 wire heating systems connect wires from heating control to Rh and W1 9 Wiring Diagrams Remove Factory Installed Jumper Transformer Common See Note 1 Cooling Heating Fan Control Neutral 120 VAC Hot Neutral 120 VAC Hot 24 VAC 24 VAC Remote Sensor NOTE 2 Conventional Systems Dual Transformer G Rc Rh W2 B O Y1 W1 E W3 C L S1 S2 Compressor Control Y2 Heat Control 2nd Stage Heat Control NOTE 4 ...

Страница 12: ...ation of thermostat 2 Second Stage Control connections not used for single stage heating or cooling systems 3 For units requiring reversing valve to be energized during heating connect reversing valve to B terminal For units requiring reversing valve to be energized during cooling connect reversing valve to O terminal 4 Required for units with 2 stage heat only 5 For 2 stage heat units not having ...

Страница 13: ... improper installation or any other failure to follow Braeburn installation and operating instructions Braeburn Systems LLC agrees to repair or replace at its option any Braeburn thermostat under warranty provided it is returned postage prepaid to our warranty facility in a padded carton within the warranty period with proof of the original date of purchase and a brief description of the malfuncti...

Отзывы: