Factory Installed Jumper

1st Stage

Compressor

Control

2nd Stage

Compressor

Control

(NOTE 2)

2nd Stage

Heat Control

(NOTE 2)

Remote

Sensor

(NOTE 3)

Tr

ansformer Commo

n

      (See Note 1)

Neutral

120 VAC

Hot

24 VAC

Conventional Systems (Single Transformer)

G

Rc

Rh

W2

B

O

Y1

W1/E/W3 C

L

S1

S2

Y2

Fan Control

1st Stage

Heat Control

NOTES:

  1.

Transformer Common connection not required for battery-only operation  

 

of thermostat. 

2.

 Second Stage Control connections not used for single stage 

 

heating or cooling systems. 

3.

 Remote Sensor Terminals can be either for Outdoor  

 

or Indoor Remote Sensor depending on installer settings. 

4. 

For millivolt or other 

 

2 wire heating systems, connect wires from heating control to Rh and W1.

9

Wiring Diagrams

Remove Factory

Installed Jumper

Tr

ansformer Commo

n

(See Note 1)

Cooling

Heating

Fan Control

Neutral

120 VAC

Hot

Neutral

120 VAC

Hot

24 VAC

24 VAC

Remote

Sensor

(NOTE 2)

Conventional Systems (Dual Transformer)

G

Rc

Rh

W2

B

O

Y1

W1/E/W3 C

L

S1

S2

Compressor

Control

Y2

Heat

Control

2nd Stage

Heat

Control

(NOTE 4)

2nd Stage

Compressor

Control

(NOTE 4)

NOTES:

  1.

 Transformer Common connection not required for battery-only operation  

 

of thermostat. 

2. 

Remote Sensor Terminals can be either for Outdoor or Indoor 

 

Remote Sensor depending on installer settings. 

3. 

For millivolt or other 2 wire  

 

heating systems, connect wires from heating control to Rh and W1. 

4.

 Second  

 

Stage Control connections not used for single stage heating or cooling systems.

Содержание Premier 3300

Страница 1: ...8 Troubleshooting 9 Wiring Diagrams 1 Specifications Electrical Rating 24 Volt AC 18 30 Volt AC 1 amp maximum load per terminal 5 amp maximum load all terminals Control Range 45º 90º F 7º C 32º C Accuracy 1º F 5º C 3 RH AC Power 18 30 Volt AC DC Power 3 0 Volt DC 2 AA Alkaline batteries included Compatibility Compatible with low voltage single stage or multi stage heat cool systems including heat ...

Страница 2: ...es in the sub base mark the placement of the mounting holes through the slots and onto the wall Ensure the wires come out of the wall into the center hole of the sub base 5 After verifying the drill will not damage items in the wall use a 3 16 drill to create the mounting holes Gently tap the supplied plastic anchors into the holes in the wall 6 Place the thermostat sub base against the wall in th...

Страница 3: ... deg No Limit Status After CLEAR Factory Default Settings At initial power up or after Installer CLEAR button is pressed the thermostat is reset to factory defaults Installer CLEAR button is located on the circuit board 3 3 Quick Reference Model 3300 shown with cover open SYSTEM Button Selects AUTO Heat Cool COOL OFF HEAT or EMER BACK Button Scrolls backwards between setup screens NEXT Button Scro...

Страница 4: ...ature display or balance point control is automatically detected Test outdoor sensor connection by pressing BACK and NEXT at the same time 13 Set Security Level sec 2 sec i Selects between level 1 or level 2 for Keypad Lock sec 2 keypad lockout 14 Dead Band a 3 a 2 Selects Auto Changeover Dead a 3 Band of 2 3 4 5 F 1 0 1 5 2 0 a 4 2 5 C Only available if Auto a 5 Changeover is enabled in option 2 ...

Страница 5: ...4 12 40 40 12 60 60 12 120 120 12 7 4 Programming Installer Settings cont Factory Installer Options Default Options Comment 15 Compressor balc O balc O Scrolls between NO no lockout Balance Point balc 1O and 10 to 50 F 12 to 10 C to balc 5O set Compressor Balance Point Only available with multi stage heat pump and outdoor sensor connected 16 Auxiliary Balance bala O bala O Scrolls between NO no lo...

Страница 6: ... button The and buttons can be pressed together to enter the lock code but the buttons do not work individually to adjust the temperature The lock security level is set in the Installer Options and the lock code is set in the User Options 14 When Auto Changeover mode is enabled and selected the system automatically switches between heating and cooling when the room temperature meets the normal cri...

Страница 7: ...digit code you have created Locking the Thermostat Press and hold the and buttons together for five seconds While you are holding these buttons the LOCK icon will flash once per second and after 5 seconds the LOCK icon and three digits will appear in the display Use the or buttons to enter the lock code you previously created see Setting Your Lock Code After entering the first digit press the NEXT...

Страница 8: ...ies to provide power for the thermostat if 24 volt AC power is not connected to the terminal block This thermostat is equipped with a unique three level low battery detection feature that constantly monitors the batteries during normal operating mode to determine whether they have sufficient power to provide proper operation When this feature determines that the battery status is low a low battery...

Страница 9: ...enough Potential Solution Increase or decrease temperature differential settings as ap propriate to provide the desired performance level See page 9 Symptom Low battery indicator is shown in thermostat display Potential Solution Replace batteries immediately to maintain proper system operation See page 14 Symptom Thermostat display is blank Potential Solution It is possible that AC power is not pr...

Страница 10: ... to enter unlock mode Press to enter the 3 digit unlock code Press the NEXT button to move to the next digit Symptom Fan continues to run all the time whether the system is on or off Potential Solution Check to make sure the fan control switch is in the AUTO posi tion This will allow the fan to run only when the heating or cooling system is turned on and running Check thermostat wiring to make sur...

Страница 11: ... other 2 wire heating systems connect wires from heating control to Rh and W1 9 Wiring Diagrams Remove Factory Installed Jumper Transformer Common See Note 1 Cooling Heating Fan Control Neutral 120 VAC Hot Neutral 120 VAC Hot 24 VAC 24 VAC Remote Sensor NOTE 2 Conventional Systems Dual Transformer G Rc Rh W2 B O Y1 W1 E W3 C L S1 S2 Compressor Control Y2 Heat Control 2nd Stage Heat Control NOTE 4 ...

Страница 12: ...ation of thermostat 2 Second Stage Control connections not used for single stage heating or cooling systems 3 For units requiring reversing valve to be energized during heating connect reversing valve to B terminal For units requiring reversing valve to be energized during cooling connect reversing valve to O terminal 4 Required for units with 2 stage heat only 5 For 2 stage heat units not having ...

Страница 13: ... improper installation or any other failure to follow Braeburn installation and operating instructions Braeburn Systems LLC agrees to repair or replace at its option any Braeburn thermostat under warranty provided it is returned postage prepaid to our warranty facility in a padded carton within the warranty period with proof of the original date of purchase and a brief description of the malfuncti...

Отзывы: