14
HL-Series Tankless Heater
Installation
3/29/2018
Bradley •
215-1823 Rev. F; ECN 18-17-017
Output heating capacity is reduced on the 480V units if these heaters are installed on 415V or 380V single or three
phase .
Contact the factory to supply this information .
Satisfactory performance of the heater is dependent upon a specific flow rate vs temperature rise capability . If the
desired temperature is not achieved, please verify the following:
1 . Circuit breaker is on and rated for the maximum power draw .
2 . Heater is drawing the proper current for the supply voltage on all the single phase or all the three phases .
3 . All phase indicator lights are lit (not flashing) indicating maximum power draw and maximum
amperage is being drawn .
4 . Flow rate and temperature rise in the water heating process are compatible with the heater specifications .
5 . Verify there is no additional supply of cold water entering the line downstream of the heater .
Product Options
AL High-Low Temperature Alarm:
Alerts user to an over or under temperature situation .
T190 High Temperature Option:
Reach and maintain temperatures as high as 190°F (88°C) .
IC Temperature Lock Out:
Temperature lock out at specific °F or °C .
Low Flow (L25 & L15):
Options include 0 .25 GPM (0 .9 lpm) and 0 .15 GPM (0 .6 lpm) for heating water at a lower
flow as required .
D1 Control Interface:
Provides 4–20ma communication interface with temperature controller .
DC Control Interface:
Is an RS-485 Modbus RTU and allows Building Management Systems to view heater outlet
temperature and heater activation via BMS display as well as change the temperature set-point from the BMS .
TE2 Corrosive Fluid Protection:
The TE2 option is a single layer of Xylan Fluoropolymeric coated heat exchanger
with bright annealed stainless steel elements, FDA Approved for Food Contact (use in deionized water applications) .
N4X (NEMA 4X Enclosure):
The optional NEMA 4X corrosion resistant enclosure is designed for harsher
environments and made from 16 gauge 304 stainless steel . The NEMA 4X enclosure can also be specified as an
upgrade with 316 stainless steel .
N4 (NEMA 4 Enclosure):
The optional 18 gauge, NEMA 4 enclosure with ANSI61 gray, corrosion resistant paint .
NEMA 4 is standard on model HL-25.