4.9.2
Gas Line Sizing Tables for LP GAS
For your convenience see below for an excerpt from gas line sizing tables for a single LP appliance. Their intended use of is for pipe sizing between the
2nd stage (low pressure) regulator and the appliance. For details see the current NFPA 54 or NFPA 58.
Specified pipe lengths are for one RTG 199ME which has a maximum input of 199,000. The gas supply system must be sized for the combined total
maximum BTU/hr load requirements of all gas appliances running simultaneously.
The tables below show the maximum capacity of the gas supply pipe in thousands of BTU per hour of Undiluted LP Gas at 11" W.C (0.4 psig or 27.4
mbar) based on a pressure drop of 0.5" W.C (1.25 mbar).
* EHD = Equivalent Hydraulic Diameter. The greater the value of EHD, the greater the gas capacity of the tubing.
Maximum Capacity of Semi-Rigid (flexible, non corrugated) Tubing in
Thousands of BTU/hr of Undiluted Liquefied Petroleum Gases (at 11
inches Water Column Inlet Pressure).(Based on a Pressure Drop of 0.5
Inch Water Column)* Source National Fuel Gas Code NFPA 54, ANSI
Z223.1 - No Additional Allowance is necessary for an ordinary number of
fittings.
4.10
Water connections
▶ When facing the heater, the ¾ ” cold connection is on the bottom
right and the hot connection is on the bottom left. Centrally locating
the water heater is recommended to keep hot water distribution
times even throughout the structure.
Fig. 34
[1]
Cold connection
[2]
Hot connection
Nominal Iron
Pipe inches
Internal
Diameter
inches
Length of Black iron Pipe, Feet
10
20
30
40
50
60
80
100
1/2
0.622
291
200
160
137
122
110
101
94
3/4
0.824
608
418
336
287
255
231
212
197
1
1.049
1150
787
632
541
480
434
400
372
Table 28
Tube size,
inches
Length of Corrugated Stainless Steel Tubing (CSST), Feet
EHD*
10
20
30
40
50
60
70
80
90
100
3/4
23
254
183
151
131
118
107
99
94
90
85
3/4
23 303
216
177
153
137
126
117
109
102
98
1
30 521
365
297
256
227
207
191
178
169
159
1
31
605
425
344
297
265
241
222
208
197
186
Table 29
Nominal Iron
Pipe inches
Internal Diameter
inches
Length of Semirigid (soft) Copper ACR Tubing, Feet
10
20
30
40
50
5/8
0.527
188
129
104
89
79
3/4
0.652
329
226
182
155
138
Table 30
NOTICE:
▶ This heater is not approved for preheated water
applications exceeding 140°F (60°C).
NOTICE:
▶ In applications where inlet water temperature can
exceed 140°F (60°C), a 3-way valve or mixing valve
must be installed before the appliance to prevent
water exceeding 140°F (60°C) from entering the
appliance.