background image

 

 

11 

 
All Air From Inside the Building:

  The confined space shall be provided 

with two permanent openings communicating directly with an additional 
room(s) of sufficient volume so that the combined volume of all spaces meets 
the criteria for an unconfined space.  The total input of all gas  
 
utilization equipment installed in the combined space shall be considered in 
making this determination.  Each opening shall have a minimum free area of 
1 square inch per 1000 BTU 

(2.54cm

2

/.29kw)

 per hour of the total input rating 

of all gas utilization equipment in the confined space, but not less than 100 
square inches 

(254cm

2

)

.  One opening shall be within 12 inches 

(31cm)

 of the 

top and one within 12 inches 

(31cm)

 of the bottom of the enclosure. 

 

All Air From Outdoors

: The confined space shall be provided with two 

permanent openings, one commencing within 12 inches 

(31cm)

 of the top and 

one commencing within 12 inches 

(31cm)

 from the bottom of the enclosure.  

The openings shall communicate directly, or by ducts, with the outdoors or 
spaces (crawl or attic) that freely communicate with the outdoors. 
1.  When directly communicating with the outdoors, each opening shall have 

a minimum free area of 1 square inch per 4000 BTU 

(2.54cm

2

/1.2kw)

 per 

hour of total input rating of all equipment in the enclosure. 

2.  When communicating with the outdoors through vertical ducts, each 

opening shall have a minimum free area of 1 square inch per 4000 BTU 

(2.54cm

2

/1.2kw)

 per hour of total input rating of all equipment in the 

enclosure. 

3.  When communicating with the outdoors through horizontal ducts, each 

opening shall have a minimum free area of 1 square inch per 2000 BTU 

(2.54cm

2

/.6kw)

 per hour of total input rating of all equipment in the 

enclosure. 

4.  When ducts are used, they shall be of the same cross-sectional area as 

the free area of the openings to which they connect.  The minimum 
dimension of rectangular air ducts shall be not less than 3 inches 

(7.5cm)

 

 

Specially Engineered Installations

 

The requirements noted under CONFINED SPACES above shall not 
necessarily govern when special engineering, approved by the authority 
having jurisdiction, provides an adequate supply of air for combustion, 
ventilation, and dilution of flue gases. 

 
 
 
 
 
 
 

 

12

 

WATER CONNECTIONS 

 
Note:  BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE 
MAIN WATER SUPPLY VALVE. 

After shutting off the main water supply, open a faucet to relieve the water 
line pressure to prevent any water from leaking out of the pipes while making 
the water connections to the water heater.  After the pressure has been 
relieved, close the faucet.  The COLD water inlet and HOT water outlet are 
identified on the top of the water heater.  The fittings at the cold water inlet 
and hot water outlet are dielectric waterway fittings with 3/4” NPT male 
thread.  Make the proper plumbing connections between the water heater and 
the plumbing system to the house.  Install a shut-off valve in the cold water 
supply line. 

 
If this water heater is installed in a closed water supply system, such as the 
one having a back-flow preventer in the cold water supply, provisions shall be 
made to control thermal expansion.  

DO NOT

 operate this water heater in a 

closed system without provisions for controlling thermal expansion.  Your 
water supplier or local plumbing inspector should be contacted on how to 
control this situation 

 

After installation of the water lines, open the main water supply valve and fill 
the water heater.  While the water heater is filling, open several hot water 
faucets to allow air to escape from the water system.  When a steady stream 
of water flows through the faucets, close them and check all water 
connections for possible leaks.

  NEVER OPERATE THE WATER HEATER 

WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER.

 

WARNING

 

FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X 3/4” 
TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE 
MANUFACTURER FROM ANY CLAIM WHICH MIGHT RESULT FROM 
EXCESSIVE TEMPERATURE AND PRESSURES.

 

CAUTION

 

If sweat fittings are to be use, 

DO NOT

 apply heat to the nipples on top of 

the water heater.  Sweat the tubing to the adapter before fitting the adapter 
to the water connections.  It is imperative that heat is not applied to the 
nipples containing a plastic liner.

 

Содержание mi5036en10

Страница 1: ...or your family s comfort safety and convenience we recommend this water heater be installed and serviced by a plumbing professional WARNING If the information in these instructions is not followed exa...

Страница 2: ...under water Depending upon the individual circumstances it may be necessary to replace the entire water heater Do not store or use gasoline or other flammable combustible or corrosive vapors and liqui...

Страница 3: ...necessary contact especially by children with the water heater and vent air intake components UNDER NO CIRCUMSTANCES SHALL FLAMMABLE MATERIALS SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN TH...

Страница 4: ...ten egg smell Other conditions such as odorant fade can cause the odorant to diminish in intensity or fade and not be as readily detectable If you have a diminished sense of smell or are in any way un...

Страница 5: ...ust be installed properly Failure to properly install the vent system could result in property damage personal injury or death 10 Combustion Air Supply Provide adequate air for combustion and ventilat...

Страница 6: ...CES above shall not necessarily govern when special engineering approved by the authority having jurisdiction provides an adequate supply of air for combustion ventilation and dilution of flue gases 1...

Страница 7: ...e is to be installed to allow for complete drainage of both the combination temperature and pressure relief valve and the discharge line The discharge opening must not be subjected to blockage or free...

Страница 8: ...talled as close to the water heater s combination gas control as possible A ground joint union must be installed in the gas supply line feeding the water heater to permit servicing of the water heater...

Страница 9: ...gas supply to the water heater 4 Close the cold water supply shut off valve 5 Open the drain valve on the water heater by turning the knob counter clockwise The drain valve has threads on the end that...

Страница 10: ...e technician Note Whenever the water heater is filled with cold water condensate will form on the cool tank surface and drops of water will fall on the hot burner and combustion chamber surfaces produ...

Страница 11: ...remove the inner door and main burner assembly to clean orifices and related parts of any dirt or other foreign material Inspect the burner ports for obstructions or debris and clean with a wire brus...

Страница 12: ...s Nights Address Supplier Supplier Phone No CAUTION FOR YOUR SAFETY DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL BURNERS OR GAS PIPING REFER REPAIRS TO A QUALIFIED SERVICE TECHNICIAN Manufactured...

Страница 13: ...Varies by Model 28 Steel Burner Varies by Model THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF GAS WATER HEATERS SUITABLE FOR WATER POTABLE HEATING AND SPACE HEATING 1 All piping components connec...

Страница 14: ...27 FIGURE 6 FIGURE 7 28 NOTES...

Отзывы: