15

 

GAS CONNECTIONS 

 

The gas supply lines must meet all requirements of the National Fuel Gas 
Code ANSI Z223.1-(Latest Edition) and/or in Canada CAN/CGA B149 
Installation Codes - (Latest Editions). 
 
The minimum permissible gas supply pressure for the purpose of input 
adjustment is 1.0” water column 

(.25kPa) 

above the operating manifold 

pressure.  See the rating plate and combination gas control for the manifold 
pressure and gas type.  The maximum permissible gas supply pressure is 
14.0” water column 

(3.5kPa) 

for natural gas and liquefied petroleum 

gases/propane gas. 
 
1.  Connect this water heater only to the type of gas (Natural or Propane gas) 

as shown on the rating plate.  Use clean 1/2 inch black iron pipe. (Dirt and 
scale from the  pipe can enter the combination control and cause it to 
malfunction).  The inlet gas line must have a minimum length of 3” 

(7.6 

cm)

 drip leg 

(sediment trap) 

installed as close to the water heater’s 

combination gas control as possible.  A ground joint union must be 
installed in the gas supply line feeding the water heater to permit 
servicing of the water heater. Compounds used on the threaded joints of 
the gas piping must be resistant to the action of liquefied petroleum 
gases/propane gas. 

2.  This water heater and its gas connection must be leak tested before 

placing the water heater in operation.  Check for gas leaks with a soap 

 

 

16 

and water solution and a brush or a commercial leak detector fluid. 

NEVER USE A MATCH OR OPEN FLAME FOR TESTING!

 

 

 
 

 
 
 

 
 
 

CAUTION 

The water heater and individual shutoff valve must be disconnected from 
the gas supply piping system during any pressure testing of the system at 
test pressures in excess of 1/2 psi 

(3.5 kPa)

.  The water heater must be 

isolated from the gas supply piping system by closing its manual shutoff 
valve during any pressure testing of the gas supply system at test 
pressures equal to or less than 1/2 psi 

(3.5 kPa)

.  The supply line must be 

capped when not connected to the water heater.

 

Содержание mi5036en10

Страница 1: ...or your family s comfort safety and convenience we recommend this water heater be installed and serviced by a plumbing professional WARNING If the information in these instructions is not followed exa...

Страница 2: ...under water Depending upon the individual circumstances it may be necessary to replace the entire water heater Do not store or use gasoline or other flammable combustible or corrosive vapors and liqui...

Страница 3: ...necessary contact especially by children with the water heater and vent air intake components UNDER NO CIRCUMSTANCES SHALL FLAMMABLE MATERIALS SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN TH...

Страница 4: ...ten egg smell Other conditions such as odorant fade can cause the odorant to diminish in intensity or fade and not be as readily detectable If you have a diminished sense of smell or are in any way un...

Страница 5: ...ust be installed properly Failure to properly install the vent system could result in property damage personal injury or death 10 Combustion Air Supply Provide adequate air for combustion and ventilat...

Страница 6: ...CES above shall not necessarily govern when special engineering approved by the authority having jurisdiction provides an adequate supply of air for combustion ventilation and dilution of flue gases 1...

Страница 7: ...e is to be installed to allow for complete drainage of both the combination temperature and pressure relief valve and the discharge line The discharge opening must not be subjected to blockage or free...

Страница 8: ...talled as close to the water heater s combination gas control as possible A ground joint union must be installed in the gas supply line feeding the water heater to permit servicing of the water heater...

Страница 9: ...gas supply to the water heater 4 Close the cold water supply shut off valve 5 Open the drain valve on the water heater by turning the knob counter clockwise The drain valve has threads on the end that...

Страница 10: ...e technician Note Whenever the water heater is filled with cold water condensate will form on the cool tank surface and drops of water will fall on the hot burner and combustion chamber surfaces produ...

Страница 11: ...remove the inner door and main burner assembly to clean orifices and related parts of any dirt or other foreign material Inspect the burner ports for obstructions or debris and clean with a wire brus...

Страница 12: ...s Nights Address Supplier Supplier Phone No CAUTION FOR YOUR SAFETY DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL BURNERS OR GAS PIPING REFER REPAIRS TO A QUALIFIED SERVICE TECHNICIAN Manufactured...

Страница 13: ...Varies by Model 28 Steel Burner Varies by Model THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF GAS WATER HEATERS SUITABLE FOR WATER POTABLE HEATING AND SPACE HEATING 1 All piping components connec...

Страница 14: ...27 FIGURE 6 FIGURE 7 28 NOTES...

Отзывы: