16

Gas Connections 

 

The gas supply lines must meet all requirements of the National Fuel Gas Code (ANSI 
Z223.1-Latest Edition), or in Canada CAN/CGA B149.1 Natural Gas Installation Code 
(Latest Edition) or CAN/CGA B149.2 Propane Installation Code (Latest Edition). 

 

The minimum permissible gas supply pressure for the purpose of input adjustment is 
one (1.0) inch 

(0.25 kPa) 

water column above the operating manifold pressure.  See 

the rating plate and gas valve for the manifold pressure and gas type.  The maximum 
permissible gas supply pressure is fourteen (14.0) inches 

(3.5 kPa)

 water column for 

natural gas and liquefied petroleum gases/propane gas. 

 

1.  Connect this water heater only to the type of gas (Natural or Propane gas) as 

shown on the rating plate.  Use clean black iron pipe or equivalent material 
approved by local codes and ordinances. (Dirt and scale from the pipe can enter 
the gas valve and cause it to malfunction).  The inlet gas line must have a 
minimum length of three (3) inches 

(7.6 cm)

 drip leg 

(sediment trap) 

installed as 

close to the water heater’s gas valve as possible.  A ground joint union must be 
installed as close to the water heater as possible in the gas supply line feeding the 
water heater to permit servicing of the water heater. Compounds used on the 
threaded joints of the gas piping must be resistant to the action of liquefied 
petroleum gases/propane gas.  DO NOT apply pipe dope to the gas valve inlet and 
make certain that no pipe dope has become lodged in the inlet screen of the gas 
valve.  Extreme care must be taken to ensure no pipe dope enters the gas valve.  
Avoid excessive torque when tightening the gas supply line to the gas valve.  
Excessive torque may result in cracking of the gas valve housing and could create 
a gas leak.  When tightening gas supply line to L.P. control, it is recommended to 
hold the inlet body of the control securely with an adequate wrench.  The 
suggested maximum torque is 31.5 ft. lbs. (

4.4 kg-m

).   

 

2.  This water heater and its gas connection must be leak tested before placing the 

water heater in operation.  Check for gas leaks with a soap and water solution and 
a brush or a commercial leak detector fluid. 

NEVER USE A MATCH OR OPEN 

FLAME FOR TESTING!

 

 
3.  While checking for leaks care must be taken to prevent solution from   

contacting the electrical connections at the control. If electrical connections at the 
control become wet, they must be thoroughly dried before attempting to operate 
the water heater.

 

 

 

WARNING 

The manufacturer of this water heater will not be liable for any damage or injury 
caused as a result of a cracked gas inlet as a result of excessive torque.

 

 

CAUTION 

The water heater and individual shutoff valve must be disconnected from the gas 
supply piping system during any pressure testing of the system at test pressures in 
excess of 1/2 psi (

3.5 kPa

).  The water heater must be isolated from the gas supply 

piping system by closing its manual shutoff valve during any pressure testing of the 
gas supply system at test pressures equal to or less than 1/2 psi (

3.5 kPa

).  The 

supply line must be capped when not connected to the water heater.

 

Содержание GAS-FIRED WATER HEATER

Страница 1: ...reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier For your family s comfort safety and convenience...

Страница 2: ...vent of improper usage or storage of gasoline or other flammable materials in the location where the water heater is installed the technology will resist ignition of the flammable vapors outside the c...

Страница 3: ...on Air Supply 11 Water Connections 13 Gas Connections 16 GENERAL OPERATION 17 Lighting and Shutdown Instructions 18 Thermostat Adjustment 19 Burner Flame Check 20 MAINTENANCE 21 INSTALLATION DRAWING F...

Страница 4: ...e to comply with these instructions This water heater is not design certified for installation in a mobile home Such an installation may create a hazardous condition and will nullify the warranty This...

Страница 5: ...on gas control A sacrificial anode is used to extend tank life The removal of this anode for any reason will nullify the warranty In areas where water is unusually active an odor may occur at the hot...

Страница 6: ...ible to gas and water supply lines DO NOT locate the water heater where water lines could be subjected to freezing temperatures Make sure the cold water pipes are not located directly above the gas co...

Страница 7: ...ith little or no odor to reveal their presence NOTE DAMAGE TO THE WATER HEATER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY DO NOT OPERATE THE WATER HEATER IF EXPOSURE HAS OR...

Страница 8: ...e purchased from your plumbing professional The drain pan must be piped to an adequate drain The piping must be at least 3 4 inch 1 9 cm in diameter and pitched for proper drainage It is recommended t...

Страница 9: ...it shall be installed on top of a metal or wood panel or equivalent extending beyond the full width and depth of the appliance by at least three 3 inches 7 6 cm in any direction or if the appliance is...

Страница 10: ...system was previously sized for another gas appliance that has been removed the venting system may now be too large Refer to the latest edition of the National Fuel Gas Code ANSI Z223 1 latest editio...

Страница 11: ...ers and flue tubes with possible damage to the water heater When an exhaust fan is installed in the same room with a heater sufficient openings for air must be provided in the walls Undersized opening...

Страница 12: ...ottom of the enclosure All Air From Outdoors The confined space shall be provided with two permanent openings one commencing within 12 inches 31cm of the top and one commencing within 12 inches 31cm f...

Страница 13: ...sion DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Your water supplier or local plumbing inspector should be contacted on how to control this...

Страница 14: ...pressure relief valve into the opening provided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with a combination temperature and pressure relief...

Страница 15: ...mixing cold and hot water in branch supply lines Such valves are available from the manufacturer of this water heater or a local plumbing supplier Please consult with a plumbing professional WARNING H...

Страница 16: ...dope has become lodged in the inlet screen of the gas valve Extreme care must be taken to ensure no pipe dope enters the gas valve Avoid excessive torque when tightening the gas supply line to the gas...

Страница 17: ...sition 3 Shut off the gas supply to the water heater 4 Close the cold water supply shut off valve 5 Open the drain valve on the water heater by turning the knob counter clockwise The drain valve has t...

Страница 18: ...s STOP Follow B in the 7 Look into sight 5 Remove outer on inner door igniter button to view pilot glass window 6 Locate piezo 9a FOR EXHIBIT A GAS CONTROLS Depress and hold down red pilot set button...

Страница 19: ...dial until the minimum acceptable temperature is achieved See figure 2 above for approximate temperature settings 160 F Control 180 F Control Figure 3 The thermostat dial is set to its lowest temperat...

Страница 20: ...nk becomes heated BURNER FLAME CHECKS Cast Iron Burner At the time of installation and at periodic intervals not more than 6 months a visual check of the main burner and pilot flames should be made to...

Страница 21: ...s listed on the water heater 5 Annually remove the inner door and main burner assembly to clean orifices and related parts of any dirt or other foreign material Inspect the burner ports for obstructio...

Страница 22: ...interval for inspection and replacement of the anode rod Contact the plumbing professional who installed the water heater or the manufacturer listed on the rating plate for anode replacement informat...

Страница 23: ...___________ Supplier Supplier Phone No ____________________________________________ CAUTION FOR YOUR SAFETY DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL BURNERS OR GAS PIPING REFER REPAIRS TO A QU...

Страница 24: ...24 INSTALLATION FOR POTABLE WATER Figure 5...

Страница 25: ...25 PARTS LIST DRAWING...

Страница 26: ...6 Flue Baffle Assembly 19 Gas Feedline to Burner 7 Dip Tube Cold Water Inlet 20 Gas Feedline to Pilot 8 Temperature and Pressure Relief Valve 21 Thermocouple Lead 9 Glass Lined Tank 22 Piezo Igniter L...

Страница 27: ...or boiler treatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a non p...

Страница 28: ...28 NOTES...

Отзывы: