Combustion Air Supply continued- 

 

Confined Spaces 

Confined spaces are spaces defined as having less than 50 ft.

3

 of space per 

1,000 BTU 

(1.41m

3

/.29kw)

 per hour of input. 

 

Unconfined Spaces

 

In unconfined spaces in buildings, infiltration may be adequate to provide air 
for combustion, ventilation and dilution of flue gases.  However, in buildings of 
tight construction (for example, weather stripping, heavily insulated, caulked, 
vapor barrier, etc.), additional air may need to be provided using the methods 
described above under CONFINED SPACES:  All Air From Outdoors or 
SPECIALLY ENGINEERED INSTALLATIONS. 

 
All Air From Inside the Building:

  The confined space shall be provided with 

two permanent openings communicating directly with an additional room(s) of 
sufficient volume so that the combined volume of all spaces meets the criteria 
for an unconfined space.  The total input of all gas utilization equipment 
installed in the combined space shall be considered in making this 
determination.  Each opening shall have a minimum free area of 1 square inch 
per 1000 BTU 

(6.45cm

2

/.29kw)

 per hour of the total input rating of all gas 

utilization equipment in the confined space, but not less than 100 square 
inches 

(645cm

2

)

.  One opening shall be within 12 inches 

(31cm)

 of the top 

and one within 12 inches 

(31cm)

 of the bottom of the enclosure. 

 

All Air From Outdoors

: The confined space shall be provided with two 

permanent openings, one commencing within 12 inches 

(31cm)

 of the top and 

one commencing within 12 inches 

(31cm)

 from the bottom of the enclosure.  

The openings shall communicate directly, or by ducts, with the outdoors or 
spaces (crawl or attic) that freely communicate with the outdoors. 
1.  When directly communicating with the outdoors, each opening shall have 

a minimum free area of 1 square inch per 4000 BTU 

(6.45cm

2

/1.2kw)

 per 

hour of total input rating of all equipment in the enclosure. 

2.  When communicating with the outdoors through vertical ducts, each 

opening shall have a minimum free area of 1 square inch per 4000 BTU 

(6.45cm

2

/1.2kw)

 per hour of total input rating of all equipment in the 

enclosure. 

3.  When communicating with the outdoors through horizontal ducts, each 

opening shall have a minimum free area of 1 square inch per 2000 BTU 

(6.45cm

2

/.6kw)

 per hour of total input rating of all equipment in the 

enclosure. 

4.  When ducts are used, they shall be of the same cross-sectional area as 

the free area of the openings to which they connect.  The minimum 
dimension of rectangular air ducts shall be not less than 3 inches 

(7.5cm)

 

 

Specially Engineered Installations

 

The requirements noted under CONFINED SPACES above shall not 
necessarily govern when special engineering, approved by the authority 
having jurisdiction, provides an adequate supply of air for combustion, 
ventilation, and dilution of flue gases.

Содержание GAS-FIRED WATER HEATER

Страница 1: ...reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier For your family s comfort safety and convenience...

Страница 2: ...vent of improper usage or storage of gasoline or other flammable materials in the location where the water heater is installed the technology will resist ignition of the flammable vapors outside the c...

Страница 3: ...on Air Supply 11 Water Connections 13 Gas Connections 16 GENERAL OPERATION 17 Lighting and Shutdown Instructions 18 Thermostat Adjustment 19 Burner Flame Check 20 MAINTENANCE 21 INSTALLATION DRAWING F...

Страница 4: ...e to comply with these instructions This water heater is not design certified for installation in a mobile home Such an installation may create a hazardous condition and will nullify the warranty This...

Страница 5: ...on gas control A sacrificial anode is used to extend tank life The removal of this anode for any reason will nullify the warranty In areas where water is unusually active an odor may occur at the hot...

Страница 6: ...ible to gas and water supply lines DO NOT locate the water heater where water lines could be subjected to freezing temperatures Make sure the cold water pipes are not located directly above the gas co...

Страница 7: ...ith little or no odor to reveal their presence NOTE DAMAGE TO THE WATER HEATER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY DO NOT OPERATE THE WATER HEATER IF EXPOSURE HAS OR...

Страница 8: ...e purchased from your plumbing professional The drain pan must be piped to an adequate drain The piping must be at least 3 4 inch 1 9 cm in diameter and pitched for proper drainage It is recommended t...

Страница 9: ...it shall be installed on top of a metal or wood panel or equivalent extending beyond the full width and depth of the appliance by at least three 3 inches 7 6 cm in any direction or if the appliance is...

Страница 10: ...system was previously sized for another gas appliance that has been removed the venting system may now be too large Refer to the latest edition of the National Fuel Gas Code ANSI Z223 1 latest editio...

Страница 11: ...ers and flue tubes with possible damage to the water heater When an exhaust fan is installed in the same room with a heater sufficient openings for air must be provided in the walls Undersized opening...

Страница 12: ...ottom of the enclosure All Air From Outdoors The confined space shall be provided with two permanent openings one commencing within 12 inches 31cm of the top and one commencing within 12 inches 31cm f...

Страница 13: ...sion DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Your water supplier or local plumbing inspector should be contacted on how to control this...

Страница 14: ...pressure relief valve into the opening provided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with a combination temperature and pressure relief...

Страница 15: ...mixing cold and hot water in branch supply lines Such valves are available from the manufacturer of this water heater or a local plumbing supplier Please consult with a plumbing professional WARNING H...

Страница 16: ...dope has become lodged in the inlet screen of the gas valve Extreme care must be taken to ensure no pipe dope enters the gas valve Avoid excessive torque when tightening the gas supply line to the gas...

Страница 17: ...sition 3 Shut off the gas supply to the water heater 4 Close the cold water supply shut off valve 5 Open the drain valve on the water heater by turning the knob counter clockwise The drain valve has t...

Страница 18: ...s STOP Follow B in the 7 Look into sight 5 Remove outer on inner door igniter button to view pilot glass window 6 Locate piezo 9a FOR EXHIBIT A GAS CONTROLS Depress and hold down red pilot set button...

Страница 19: ...dial until the minimum acceptable temperature is achieved See figure 2 above for approximate temperature settings 160 F Control 180 F Control Figure 3 The thermostat dial is set to its lowest temperat...

Страница 20: ...nk becomes heated BURNER FLAME CHECKS Cast Iron Burner At the time of installation and at periodic intervals not more than 6 months a visual check of the main burner and pilot flames should be made to...

Страница 21: ...s listed on the water heater 5 Annually remove the inner door and main burner assembly to clean orifices and related parts of any dirt or other foreign material Inspect the burner ports for obstructio...

Страница 22: ...interval for inspection and replacement of the anode rod Contact the plumbing professional who installed the water heater or the manufacturer listed on the rating plate for anode replacement informat...

Страница 23: ...___________ Supplier Supplier Phone No ____________________________________________ CAUTION FOR YOUR SAFETY DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL BURNERS OR GAS PIPING REFER REPAIRS TO A QU...

Страница 24: ...24 INSTALLATION FOR POTABLE WATER Figure 5...

Страница 25: ...25 PARTS LIST DRAWING...

Страница 26: ...6 Flue Baffle Assembly 19 Gas Feedline to Burner 7 Dip Tube Cold Water Inlet 20 Gas Feedline to Pilot 8 Temperature and Pressure Relief Valve 21 Thermocouple Lead 9 Glass Lined Tank 22 Piezo Igniter L...

Страница 27: ...or boiler treatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a non p...

Страница 28: ...28 NOTES...

Отзывы: