VII - GAS PRESSURE SETTING PROCEDURE
WARNING
Dip switched #7 and #8 (combustion control switches) MUST
be returned to the "OFF" position, after setting pressures.
Dip switch #1 MUST be returned to the proper position
based upon the length of vent pipe (see page 13).
Refer to page 12 for factory default dip switch settings.
8.
Turn off the gas to the water heater. Remove the manometer connection. Reinstall the
pressure port plug.
Turn on the gas to the water heater and check for gas leaks around test port with a leak
solution.
9.
Reinstall the front cover and place the unit back into operation.
10.
Verify the proper water temperature, as set on the controller at your outlets.
If controllers are not being used the output temperature should be 120°F for residnetial
models or 140˚ for commercial models.
Содержание Everhot IGI-180C-5N
Страница 7: ...I GENERAL INFORMATION cont CUT AWAY ILLUSTRATION 7...
Страница 8: ...I GENERAL INFORMATION cont SCHEMATIC ILLUSTRATION 8...
Страница 21: ...V SEQUENCE OF OPERATION cont Operation Sequence Flow Chart 21...
Страница 22: ...V SEQUENCE OF OPERATION cont Operation Sequence Flow Chart 22...
Страница 23: ...V SEQUENCE OF OPERATION cont Sequence Timing Chart 23...
Страница 24: ...V SEQUENCE OF OPERATION cont Sequence Timing Chart 24...
Страница 30: ...Wiring Schematic 30...
Страница 55: ...55 X PARTS BREAKDOWN Disassembled View Cabinet...
Страница 56: ...X PARTS BREAKDOWN Disassembled View Internals 56...
Страница 57: ...X PARTS BREAKDOWN Disassembled View Internals 57...
Страница 58: ...X PARTS BREAKDOWN Disassembled View Electrical 58...
Страница 62: ...62 Notes...
Страница 63: ...63 Notes...