2) Is the flame rod normal ? Error “72” is displayed
3) Is the water temperature thermistor normal?
38
Checking the flame rod.
a.
# Detach the flame rod terminal C1, and re-attempt
operation.
(“72 is displayed)
Proceed to check item 3 below.
(no “72” displayed)
Inspect flame rod wiring for current leak and inspect
flame rod for carbon build-up.
Measure resistance between the flame rod
Terminal C1 and the appliance earth.
Normal:
1 M Ω or more.
If normal, replace the PCB unit.
Faulty
: Replace the flame rod.
(Service Procedure IGI-2, page 49)
See page 42 for additional information and resistance values
pertaining to the flame rod.
If error “32” is displayed, check the water
temperature thermistor.
a.
# Disconnect connector B5, and measure resistance of
the white ~ white wires.
Resistance > 1 M Ω = open circuit.
Resistance < 1 Ω = short circuit.
Normal:
Proceed to check item 4 on the next page.
Faulty:
Replace the water temperature thermistor.
(Service Procedure IGI-6, page 50)
See page 43 for additional information and
resistance readings pertaining to the
temperature themistor.
VI - TROUBLESHOOTING
(cont.)
BEFORE CARRYING OUT CHECKS MARKED WITH A # SIGN, DISCONNECT THE POWER SUPPLY.
Содержание Everhot IGI-180C-5N
Страница 7: ...I GENERAL INFORMATION cont CUT AWAY ILLUSTRATION 7...
Страница 8: ...I GENERAL INFORMATION cont SCHEMATIC ILLUSTRATION 8...
Страница 21: ...V SEQUENCE OF OPERATION cont Operation Sequence Flow Chart 21...
Страница 22: ...V SEQUENCE OF OPERATION cont Operation Sequence Flow Chart 22...
Страница 23: ...V SEQUENCE OF OPERATION cont Sequence Timing Chart 23...
Страница 24: ...V SEQUENCE OF OPERATION cont Sequence Timing Chart 24...
Страница 30: ...Wiring Schematic 30...
Страница 55: ...55 X PARTS BREAKDOWN Disassembled View Cabinet...
Страница 56: ...X PARTS BREAKDOWN Disassembled View Internals 56...
Страница 57: ...X PARTS BREAKDOWN Disassembled View Internals 57...
Страница 58: ...X PARTS BREAKDOWN Disassembled View Electrical 58...
Страница 62: ...62 Notes...
Страница 63: ...63 Notes...