Page 15
The Brute Elite 125
SECTION 5.
Pump Capacity
5.1 Brute Elite Heating System
Pump Capacity
HEATING
DHW
SIZE
CONN SIZE
CONN SIZE
125
3/4"
1/2"
Table 7. Water Connection Pipe Sizes.
when rigid hangers are installed. Maintain 1" (2.5cm)
clearance to combustibles for hot water pipes.
Pipe the discharge of the pressure relief valve (full
size) to a drain or in a manner to prevent injury in the
event of pressure relief. If system contains more than
24 gallons (91 liters), then an auxiliary expansion tank
is required. Minimum fill pressure must be 12psig
(82.7kPa). Install shutoff valves where required by code.
Suggested piping diagrams are shown in
Figures
12 through 19
. These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
Brute Elite's efficiency is higher with lower
return water temperatures.
Brute Elite MUST be piped in a primary-secondary
fashion (using either piping or a hydraulic separator)
such that the pump that is mounted on the boiler ONLY
serves the boiler.
Brute Elite boiler must be located within 15 feet
(4.6m) of the supply and return header (or the hydraulic
separator). The pump is sized for a maximum of 30 feet
(9.1m) of piping and the headloss of the boiler only.
For custom configurations, the available pump
head is provided in
Figure 11.
The system designer
should take into account allowable boiler temperature
rise of 65°F (36°C).
6.2 Cold Water Make-Up
1. Connect the cold water supply to the inlet
connection of an automatic fill valve.
2. Install a suitable back flow preventer between the
automatic fill valve and the cold water supply.
3. Install shut off valves where required.
Figure 11. Available Pump Head.
Figure 12. DHW Connections with Anti-Scald Valve and
Flow Restrictor.
SECTION 6.
Water Connections
6.1 Central Heat System Piping
NOTE:
This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7kPa)
static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
PRV
Included with
Brute Elite
A Pressure Relief Valve
is included with each Brute
Elite. The PRV must be installed prior to filling the system.
Содержание brute elite 125 BLMH
Страница 42: ...Page 40 Bradford White Corp Figure 28 Panel Assembly Door Top...
Страница 43: ...Page 41 The Brute Elite 125 Figure 29 Panel Assembly Door Middle...
Страница 44: ...Page 42 Bradford White Corp Figure 30 Panel Assembly Door Bottom...
Страница 45: ...Page 43 The Brute Elite 125 Figure 31 Base Jacket Assembly...
Страница 46: ...Page 44 Bradford White Corp Figure 32 Heat Exchanger Cabinet Fan...
Страница 47: ...Page 45 The Brute Elite 125 Figure 33 Heat Exchanger Burner Components...
Страница 48: ...Page 46 Bradford White Corp Figure 34 Pump Assembly Components...
Страница 49: ...Page 47 The Brute Elite 125 Figure 35 Plumbing Components...
Страница 50: ...Page 48 Bradford White Corp...
Страница 51: ...Page 49 The Brute Elite 125...