Page 26
Bradford White Corp.
SECTION 8.
Control Setup and Operation
The Brute Elite control is an integrated electronic
control that replaces many of the individual components
found on older appliances. The control acts as the
ignition control, pump control, high limit and cascading/
lead lag control and is setup using the digital display on
the appliance.
8.1 Digital Display Navigation
The Digital Display is centered in the middle of
the User Interface and has 3 seperate modes of control.
They are USER, SETUP and DIAGNOSTIC. The names
of these modes clearly labels the intent of the different
levels of control. A USER might be the homeowner or
a service technician. SETUP displays all the controls
needed when setting up or expanding the boiler. And
DIAGNOSTIC is intended for a trained Brute Elite
technician. The menu structure and variables in each are
shown in
Table 9, Table 10, and Table 11
.
USER Mode is the home screen shown on the
control. If the display is not in USER Mode wait for the
display timeout period to be reached or press the Done
button to return to the USER Mode.
SETUP Mode is accessed by holding the up and
down arrow keys simultaneously for 3 seconds.
DIAGNOSTIC Mode is accessed by holding the
NEXT button for 3 seconds
Once in a particular Mode, navigation consists of
pressing the next button to scroll from item to item and
then pressing the up and down arrows to change values.
Once the value is adjusted, the NEXT or DONE button
can be pressed.
Figure 23. The
USER INTERFACE
.
MENU ITEM
DEFINITION
F or C
Selects temperature units
LBTHODLOD Outdoor reset enable/disable -
enables menu items
LBT
Low boiler setpoint during outdoor reset
HOD
High outdoor temperature setpoint
LOD
Low outdoor temperature setpoint
RMT Add
Used for Lead/Lag (follow menus)
LL
Lead/Lag enable/disable - enables menu items
HS
Hysteresis - temp range between on/off cycles
bL
Base Load % - input rate before next boiler fires
Sd
Warm weather shut-down temperature
ASC
Anti short cycle - minutes of delay between
startup
bAC
Future use - Press DONE to exit menu.
PAS
Future use - Press DONE to exit menu.
NOTE:
When enabling/disabling functions, select "Done" and wait 30
seconds before scrolling.
Table 10. SETUP Mode Parameters.
MENU ITEM
FUNCTION
RANGE
DEFAULT
Outlet water Displays the current outlet 55-180°F 120°F
temperature water temperature & allows
the setpoint to be adjusted
Inlet water
Displays the current inlet
—
—
temperature water temperature
Delta T
Displays the current
—
—
temperature rise across
the heat exchanger
Stack
Displays the current stack
—
—
temperature temperature
Outdoor
Displays the current outdoor
—
—
temperature air temperature
Firing Rate Displays an indicator of the
—
—
current firing rate based
upon fan RPM. The actual
firing rate may vary.
Table 9. USER Mode Menu.
MENU ITEM
DESCRIPTION
mA
Display the flame sense signal
Alert codes
Displays the current alert code
Lockout code
Displays the current lockout code
Outlet limit
Displays outlet temperature limit
DHW limit
Displays Domestic Hot Water limit setting
DHW actual
Displays Actual DHW temperature
Stack limit
Displays
Stack limit setting
Min. firing rate Displays the minimum firing rate allowed
Min. forced
Allows the user to force the boiler to fire at
firing rate
the minimum firing rate
Max forced
Allows the user to force the boiler to fire at
firing rate
the maximum firing rate
Rate indicator Displays a indicator of the firing rate based
off of the fan RPM. Actual firing rate may
vary depending upon setup.
Table 11. DIAGNOSTIC Mode Menu.
Содержание brute elite 125 BLMH
Страница 42: ...Page 40 Bradford White Corp Figure 28 Panel Assembly Door Top...
Страница 43: ...Page 41 The Brute Elite 125 Figure 29 Panel Assembly Door Middle...
Страница 44: ...Page 42 Bradford White Corp Figure 30 Panel Assembly Door Bottom...
Страница 45: ...Page 43 The Brute Elite 125 Figure 31 Base Jacket Assembly...
Страница 46: ...Page 44 Bradford White Corp Figure 32 Heat Exchanger Cabinet Fan...
Страница 47: ...Page 45 The Brute Elite 125 Figure 33 Heat Exchanger Burner Components...
Страница 48: ...Page 46 Bradford White Corp Figure 34 Pump Assembly Components...
Страница 49: ...Page 47 The Brute Elite 125 Figure 35 Plumbing Components...
Страница 50: ...Page 48 Bradford White Corp...
Страница 51: ...Page 49 The Brute Elite 125...