1.7  Locating Pump-Mounted Boiler with 

Respect to Return/Supply Header

For the best results, a pump-mounted Brute Deluxe 

Boiler should be located within 15 feet (4.6m) of the 

supply and return headers. The pump is sized for 30 feet 

(9.1m) of piping.

If the appliance must be installed with longer 

piping runs, then larger diameter tubing shall be used. 

Consult the factory for assistance.

1.8  Locating Appliance for Correct 

Horizontal Vent/Ducted Air Distance 

from Outside Wall

The forced draft combustion air blower/blowers 

in the appliance has/have sufficient power to pull air 

and vent properly when the following guidelines for 

horizontal air and vent are followed (

see Table 2

).

NOTE:

 The vent collar size is larger than the size of 

the vent pipe that can be used. Vent collar size and 

horizontal pipe diameters can be found in 

Table 2

. The 

larger vent collar size is to accommodate Category I 

(vertical) vent systems.

NOTE:

 When located on the same wall, the Brute 

Deluxe combustion air intake terminal must be installed 

a minimum of 12" (30cm) below the exhaust vent 

terminal and separated by a minimum of 36 inches 

(91cm) horizontally.

The air intake terminal must be installed high 

enough to avoid blockage from snow, leaves and other 

debris.

SECTION 2. 

Venting and Combustion Air

2.1  Combustion Air

Brute Deluxe boilers and water heaters must 

have provisions for combustion and ventilation air 

in accordance with section 5.3, Air for Combustion 

and Ventilation, of the National Fuel Gas Code, ANSI 

Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1, 

Installation Codes, or applicable provisions of the local 

building codes.

A Brute Deluxe appliance may receive combustion 

air from the space in which it is installed, or it can be 

ducted directly to the unit from the outside. Ventilation 

air must be provided in either case.

2.1.1  Combustion Air From Room

In the United States, the most common 

requirements specify that the space shall communicate 

with the outdoors in accordance with method 1 or 2, 

which follow. Where ducts are used, they shall be of the 

same cross-sectional area as the free area of the openings 

to which they connect.

Method 1

: Two permanent openings, one 

commencing within 12 inches (30 cm) of the top and one 

commencing within 12 inches (30 cm) of the bottom, 

of the enclosure shall be provided. The openings shall 

communicate directly, or by ducts, with the outdoors 

or spaces that freely communicate with the outdoors. 

When directly communicating with the outdoors, or 

when communicating to the outdoors through vertical 

ducts, each opening shall have a minimum free area of 

1 square inch per 4000 BTU/hr (5.5 square cm/kW) of 

total input rating of all equipment in the enclosure. When 

communicating to the outdoors through horizontal ducts, 

each opening shall have a minimum free area of not less 

than 1 square inch per 2000 BTU/hr (11 square cm/kW) 

of total input rating of all equipment in the enclosure. 

Table 3

 shows data for this sizing method, for each Brute 

Deluxe model.

Method 2

: One permanent opening, commencing 

within 12 inches (30 cm) of the top of the enclosure, 

shall be permitted. The opening shall directly 

communicate with the outdoors or shall communicate 

through a vertical or horizontal duct to the outdoors or 

spaces that directly communicate with the outdoors and 

shall have a minimum free area of 1 square inch per 

3000 BTU/hr (7 square cm/kW) of the total input rating 

of all equipment located in the enclosure. This opening 

must not be less than the sum of the areas of all vent 

connectors in the confined space.

Other methods of introducing combustion and 

ventilation air are acceptable, providing they conform to 

the requirements in the applicable codes listed above.

In Canada, consult local building and safety codes 

or, in absence of such requirements, follow CSA B149.1.

2.1.2  Intake Combustion Air

The combustion air can be taken through the wall, 

or through the roof. When taken from the wall, it must 

be taken from out-of-doors by means of the Bradford 

White horizontal wall terminal (

see Table 2

). When 

taken from the roof, a field-supplied rain cap or an elbow 

arrangement must be used to prevent entry of rain water 

 

UNIT 

EACH OPENING*

 

SIZE 

SQUARE INCHES 

SQUARE CM

 

500 

125 

807

 

750 

188 

1213

  1000 

250 

1613

 1250 

313 

2020

  1500 

375 

2420

  1750 

438 

2826

  2000 

500 

3226

*Net Free Area in Square Inches / Square cm

Area indicated is for one of two openings; one at floor level and one 

at the ceiling, so the total net free area could be double the figures 

indicated.
This chart is for use when communicating directly with the 

outdoors. For special conditions and alternate methods, refer to the 

latest edition of ANSI Z223.1.

Note:

  Check with louver manufacturers for net free area of 

louvers. Correct for screen resistance to the net free area if a 

screen is installed. Check all local codes applicable to combustion air.

Table 3. Combustion Air Openings.

Содержание BRUTE DELUXE BMT2H

Страница 1: ...r d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne to...

Страница 2: ...Heaters 4B 1 Water System Piping Water Heater 14 4B 2 Hot Water Supply Piping Water Heater 15 4B 3 Water Flow Requirements Water Heater 15 4B 4 Combined Water Heating potable and Space Heating Water H...

Страница 3: ...White factory or local factory representative with any issues or questions regarding this equipment Experience has shown that most operating issues are caused by improper installation The Brute Delux...

Страница 4: ...ry items are shipped in separate packages Verify receipt of all packages listed on the packing slip Inspect everything for damage immediately upon delivery and advise the carrier of any shortages or d...

Страница 5: ...ump is sized for 30 feet 9 1m of piping If the appliance must be installed with longer piping runs then larger diameter pipe or tubing shall be used Consult the factory for assistance Figure 1 Dimensi...

Страница 6: ...gure 2 Dimensional Data pump mounted models HORIZONTAL INTAKE AIR VENT COLLAR VENT PIPE PIPE MAX PIPE MAX NO SIDE WALL SIDE WALL SIZE SIZE DIAMETER DIAMETER LENGTH OF ELBOWS VENT COMBUSTION TERMINAL A...

Страница 7: ...ings shall communicate directly or by ducts with the outdoors or spaces that freely communicate with the outdoors When directly communicating with the outdoors or when communicating to the outdoors th...

Страница 8: ...he vent system must conform to the National Fuel Gas Code ANSI Z223 1 Latest Edition in the U S or in Canada to CSA B149 1 latest edition The vent system must be sized and installed for a Category I F...

Страница 9: ...appliances with condensing vents are not permitted to terminate above a public walkway or over an area where condensate or vapor could create a nuisance or hazard 3 Locate the vent terminal so that v...

Страница 10: ...t 3 feet 91 cm above if within 10 feet 3 m 6 feet 1 83 m horizontally Vent termination not allowed in this location Vent termination not allowed in this location for category IV appliances A vent shal...

Страница 11: ...ight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half in...

Страница 12: ...fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Foll...

Страница 13: ...ring any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 45kpa 9 The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during an...

Страница 14: ...he system To ensure a proper operating temperature leading to long boiler life a flow rate has been established based on the fluid temperature rise for this specific size boiler Pump mounted boilers c...

Страница 15: ...including copper if the water is moved too quickly The water flow requirements for the Brute Deluxe water heater are based upon the hardness of the water The water flow is kept high enough to prevent...

Страница 16: ...Page 16 Bradford White Corp Figure 6 Hydronic Piping Multiple Boilers Primary Secondary System Figure 7 Hydronic Piping Multiple Boilers Low Temperature System...

Страница 17: ...Page 17 Brute Deluxe 500 2000 Install Operating Figure 8 Hydronic Piping One Boiler Multi Temperature System Figure 9 Hydronic Piping Primary Secondary Reverse Return...

Страница 18: ...Page 18 Bradford White Corp Figure 10 Hydronic Piping Primary Secondary Reverse Return Low Temperature Figure 11 Water Heater Piping One Heater One Tank...

Страница 19: ...Page 19 Brute Deluxe 500 2000 Install Operating Figure 12 Water Heater Piping Multiple Heaters One Tank Figure 13 Water Heater Piping One Heater Multiple Tanks...

Страница 20: ...19 170 257 341 0 6 1 1 1 9 21 14 10 1250 68 68 90 3 8 3 8 6 3 31 31 24 257 257 341 1 2 1 2 1 9 17 17 13 1500 68 68 90 3 9 3 9 6 5 38 38 28 257 257 341 1 2 1 2 2 0 21 21 16 1750 68 68 90 4 0 4 0 6 7 4...

Страница 21: ...rk on or around the boiler may be standing on wet floors and could be electrocuted by an ungrounded boiler Single pole switches including those of safety controls and protective devices must not be wi...

Страница 22: ...BLOWER 1 LOW HIGH LOW HIGH K1 K2 K1 K2 F2 35 67 F2 35 67 F1 35 67 F1 35 67 K3 HSI 2 HSI 1 120 VAC DPDT MAIN POWER SWITCH S2 S2 35 67 35 67 L2 35 67 L2 35 67 BD 1 IGN S1 S1 35 67 35 67 35 67 L1 35 67 J...

Страница 23: ...Page 23 Brute Deluxe 500 2000 Install Operating Figure 19 Brute Deluxe 500 750 Connection Diagram...

Страница 24: ...Page 24 Bradford White Corp Figure 20 Brute Deluxe 1000 Connection Diagram...

Страница 25: ...K W L2 LOAD 1 1 2 3 4 5 6 7 8 9 10 10 lockout indicator T stat lockout indicator G Pressure Switch Gas Valve 24V Ground Remote Sense S1 L1 L2 S2 Fenwal F1 F2 lockout indicator T stat lockout indicator...

Страница 26: ...tiple boiler control BAS etc wire Stage 1 to the terminals marked Input Stage 1 and Stage 1 and wire Stage 2 to the terminals marked Input Stage 2 and Stage 2 The Local Remote selector switch above th...

Страница 27: ...ll bleeding devices and open make up water valve Allow system to fill slowly 2 If make up water pump is employed adjust pressure switch on pumping system to provide a minimum of 12 psi 81 8 kPa at the...

Страница 28: ...but with differing reductions in output At elevations higher than 7700 ft 2347 m the reduction in output will exceed 10 and at elevations below 7700 ft 2347 m it will be less than 10 High altitude adj...

Страница 29: ...ist in these adjustments are a CO2 or O2 Analyzer and a U Tube Manometer or other device capable of reading a pressure of 2 5 3 0 inches W C 0 62 0 75 kPa Start the adjustment process by checking the...

Страница 30: ...ore and after the valve and remove the valve Re install in reverse order Ensure o rings are properly installed for both inlet and outlet Turn on manual gas shutoff valve and 120 volt power and check a...

Страница 31: ...al gas valve on the heater 3 Disconnect and remove the wires conduit and sensors from all components that are attached to the inlet outlet header 4 Isolate the heat exchanger from the water supply 5 D...

Страница 32: ...esentative to discuss possible remedies 8 4 Short Cycling Water Heater Short cycling will generally occur only in combination space heating and water heating applications when the water heater is oper...

Страница 33: ...F3015 5F3015 5F3015 13 Cover Housing Pump 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 14 Cover Pipe Gas Manifold 5F3304 5F3304 10F3304 20F3304 20F3304 20F3304 20F3304 2 2 2 2 2 2 2 Internal Compo...

Страница 34: ...2018000 T2017400 T2018000 T2017400 45 Tile Bottom Center T2015900 T2015900 T2015900 T2015900 1 1 2 2 Gas Train Components See Figure 24 46 Blower A2111900 A2111900 A2111900 A2111900 A2111900 A2111900...

Страница 35: ...59 Low Water Cutoff optional E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 60 Gauge Temperature Pressure A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 62 Tee Adapter...

Страница 36: ...E0093200 E0093200 E0093200 79 Panel Mounting Limits Ignition Control 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 80 Panel Cover High Limit Ignition Control 5F7003 5F7003 5F7003 5F7003 5F7003 5F70...

Страница 37: ...Page 37 Brute Deluxe 500 2000 Install Operating Figure 23 Sheet Metal Components...

Страница 38: ...Page 38 Bradford White Corp Figure 24 Internal Components...

Страница 39: ...001800 1250 A2001800 1500 A2001900 1750 A2001900 2000 A2109700 Brute Deluxe Water Heater Size Pump p n Soft Water Normal Water Hard Water 500 A2001700 A2001700 A2001900 750 A2001700 A2001700 A2001900...

Страница 40: ...Bradford White Corporation reserves the right to change specifications components features or to discontinue products without notice 200 Lafayette St Middleville MI 49333 Warranty 800 531 2111 www Br...

Отзывы: