Brute Deluxe

 (

500-2000), Install & Operating

down aside the boiler. This is available as a Commercial 

Kit from the manufacturer. 

Part numbers for the low profile terminals to cover the 

vent and combustion air openings are shown in Table 6.

SECTION 3. 

Gas Supply and Piping

3.1  Gas Supply and Piping

Gas piping should be supported by suitable hangers 

or floor stands, not by the appliance.

Brute Deluxe’s gas train allows the user to pipe the 

gas from either the right side or the left side of the unit. 

As shipped, the right side of the gas train is capped off, 

and there is a manual valve on the left side. If desired, 

the manual valve on the left side of the gas train may 

be moved to the right side, and the cap on the right side 

may be moved to the left. 

Review the following instructions before 

proceeding with the installation.
1.  Verify that the appliance is fitted for the proper type 

of gas by checking the rating plate. Brute Deluxe 

appliances are equipped to operate at elevations up 

to 10,000 feet (3050m). Brute Deluxe appliances 

may be adjusted to operate properly at altitudes 

above 2500 feet (see 

Section 6.6.2

) and the input 

will be reduced if the heating value of the gas 

supply is below sea level values.

2.  The maximum inlet gas pressure must not exceed 

13" W.C (3.2kPa). The minimum inlet gas pressure 

is 5" W.C. (1.2kPa).

3.  Refer to 

Table 7

, size supply.

4.  Run gas supply line in accordance with all 

applicable codes.

5.  Locate and install manual shutoff valves in 

accordance with state and local requirements.

6.  A sediment trap must be provided upstream of the 

gas controls.

7.  All threaded joints should be coated with piping 

compound resistant to action of liquefied petroleum 

gas.

8.  The appliance and its individual shutoff valve must 

be disconnected from the gas supply piping during 

any pressure testing of that system at test pressures 

in excess of 1/2 PSIG (3.45kpa).

9.  The unit must be isolated from the gas supply 

system by closing its individual manual shutoff 

valve during any pressure testing of the gas supply 

piping system at test pressures equal to or less than 

1/2 PSIG (3.45kpa).

10.  The appliance and its gas connection must be leak 

tested before placing it in operation.

11.  Purge all air from gas lines.

 WARNING

Do not use open flame to check for leaks. An open 

flame could lead to explosion, which could result in 

property damage, serious injury or death.

NOTE

: The Brute Deluxe appliance and all other gas 

appliances sharing the gas supply line must be firing at 

maximum capacity to properly measure the inlet supply 

pressure. The pressure can be measured at the supply 

pressure port on the gas valve. Low gas pressure could 

be an indication of an undersized gas meter, undersized 

gas supply lines and/or an obstructed gas supply line.

SECTION 4A.

 

Unit 

20°F  25°F  30°F 35°F

 

Size 

flow 

H/L 

flow 

H/L 

flow 

H/L 

flow 

H/L

   

gpm  feet  gpm feet gpm feet gpm feet

  500 

43 

1.7 

34 

1.1 

28 

0.9 

24 

0.7

  750 

64 

3.3 

51 

2.3 

43 

1.7 

36 

1.2

  1000 

85 

5.0 

68 

3.6 

57 

3.1 

49 

2.2

  1250 

106  8.1 

85 

6.1 

71 

4.7 

61 

3.4

  1500 

128  10.0  102  7.2 

85 

5.5 

73 

4.2

  1750  N/R  N/R  119  10.5  99 

8.4 

85 

5.8

  2000  N/R  N/R  136  12.5  113  10.4  97 

8.3

 Metric Equivalent

 Unit 

11°C 

14°C 

17°C 

19°C

 

Size 

flow 

H/L 

flow 

H/L 

flow 

H/L 

flow 

H/L

    lpm  m  lpm m lpm m lpm m

  500 

161  0.5  129  0.3  107  0.3 

92 

0.2

  750 

241  1.0  193  0.7  161  0.5  138  0.4

  1000 

321  1.5  257  1.1  214  0.9  184  0.7

  1250 

401  2.5  322  1.9  269  1.4  231  1.0

  1500 

483  3.0  386  2.2  322  1.7  276  1.3

  1750 

N/R  N/R  451  3.2  375  2.6  322  1.8

  2000 

N/R  N/R  515  3.8  429  3.2  368  2.5

Notes: gpm = gallons per minute, lpm = liters per minute, 

H/L = headloss, ft = headloss in feet, m = headloss in meters.

Maximum temperature rise is 35°F (19°C), as shown. Headloss is 

for boiler’s heat exchanger only. N/R = not recommended.

Table 8. Water Flow Requirements — BMT2H.

Figure 5. Typical Gas Train Configuration.

Содержание BRUTE DELUXE BMT2H

Страница 1: ...r d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne to...

Страница 2: ...Heaters 4B 1 Water System Piping Water Heater 14 4B 2 Hot Water Supply Piping Water Heater 15 4B 3 Water Flow Requirements Water Heater 15 4B 4 Combined Water Heating potable and Space Heating Water H...

Страница 3: ...White factory or local factory representative with any issues or questions regarding this equipment Experience has shown that most operating issues are caused by improper installation The Brute Delux...

Страница 4: ...ry items are shipped in separate packages Verify receipt of all packages listed on the packing slip Inspect everything for damage immediately upon delivery and advise the carrier of any shortages or d...

Страница 5: ...ump is sized for 30 feet 9 1m of piping If the appliance must be installed with longer piping runs then larger diameter pipe or tubing shall be used Consult the factory for assistance Figure 1 Dimensi...

Страница 6: ...gure 2 Dimensional Data pump mounted models HORIZONTAL INTAKE AIR VENT COLLAR VENT PIPE PIPE MAX PIPE MAX NO SIDE WALL SIDE WALL SIZE SIZE DIAMETER DIAMETER LENGTH OF ELBOWS VENT COMBUSTION TERMINAL A...

Страница 7: ...ings shall communicate directly or by ducts with the outdoors or spaces that freely communicate with the outdoors When directly communicating with the outdoors or when communicating to the outdoors th...

Страница 8: ...he vent system must conform to the National Fuel Gas Code ANSI Z223 1 Latest Edition in the U S or in Canada to CSA B149 1 latest edition The vent system must be sized and installed for a Category I F...

Страница 9: ...appliances with condensing vents are not permitted to terminate above a public walkway or over an area where condensate or vapor could create a nuisance or hazard 3 Locate the vent terminal so that v...

Страница 10: ...t 3 feet 91 cm above if within 10 feet 3 m 6 feet 1 83 m horizontally Vent termination not allowed in this location Vent termination not allowed in this location for category IV appliances A vent shal...

Страница 11: ...ight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half in...

Страница 12: ...fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Foll...

Страница 13: ...ring any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 45kpa 9 The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during an...

Страница 14: ...he system To ensure a proper operating temperature leading to long boiler life a flow rate has been established based on the fluid temperature rise for this specific size boiler Pump mounted boilers c...

Страница 15: ...including copper if the water is moved too quickly The water flow requirements for the Brute Deluxe water heater are based upon the hardness of the water The water flow is kept high enough to prevent...

Страница 16: ...Page 16 Bradford White Corp Figure 6 Hydronic Piping Multiple Boilers Primary Secondary System Figure 7 Hydronic Piping Multiple Boilers Low Temperature System...

Страница 17: ...Page 17 Brute Deluxe 500 2000 Install Operating Figure 8 Hydronic Piping One Boiler Multi Temperature System Figure 9 Hydronic Piping Primary Secondary Reverse Return...

Страница 18: ...Page 18 Bradford White Corp Figure 10 Hydronic Piping Primary Secondary Reverse Return Low Temperature Figure 11 Water Heater Piping One Heater One Tank...

Страница 19: ...Page 19 Brute Deluxe 500 2000 Install Operating Figure 12 Water Heater Piping Multiple Heaters One Tank Figure 13 Water Heater Piping One Heater Multiple Tanks...

Страница 20: ...19 170 257 341 0 6 1 1 1 9 21 14 10 1250 68 68 90 3 8 3 8 6 3 31 31 24 257 257 341 1 2 1 2 1 9 17 17 13 1500 68 68 90 3 9 3 9 6 5 38 38 28 257 257 341 1 2 1 2 2 0 21 21 16 1750 68 68 90 4 0 4 0 6 7 4...

Страница 21: ...rk on or around the boiler may be standing on wet floors and could be electrocuted by an ungrounded boiler Single pole switches including those of safety controls and protective devices must not be wi...

Страница 22: ...BLOWER 1 LOW HIGH LOW HIGH K1 K2 K1 K2 F2 35 67 F2 35 67 F1 35 67 F1 35 67 K3 HSI 2 HSI 1 120 VAC DPDT MAIN POWER SWITCH S2 S2 35 67 35 67 L2 35 67 L2 35 67 BD 1 IGN S1 S1 35 67 35 67 35 67 L1 35 67 J...

Страница 23: ...Page 23 Brute Deluxe 500 2000 Install Operating Figure 19 Brute Deluxe 500 750 Connection Diagram...

Страница 24: ...Page 24 Bradford White Corp Figure 20 Brute Deluxe 1000 Connection Diagram...

Страница 25: ...K W L2 LOAD 1 1 2 3 4 5 6 7 8 9 10 10 lockout indicator T stat lockout indicator G Pressure Switch Gas Valve 24V Ground Remote Sense S1 L1 L2 S2 Fenwal F1 F2 lockout indicator T stat lockout indicator...

Страница 26: ...tiple boiler control BAS etc wire Stage 1 to the terminals marked Input Stage 1 and Stage 1 and wire Stage 2 to the terminals marked Input Stage 2 and Stage 2 The Local Remote selector switch above th...

Страница 27: ...ll bleeding devices and open make up water valve Allow system to fill slowly 2 If make up water pump is employed adjust pressure switch on pumping system to provide a minimum of 12 psi 81 8 kPa at the...

Страница 28: ...but with differing reductions in output At elevations higher than 7700 ft 2347 m the reduction in output will exceed 10 and at elevations below 7700 ft 2347 m it will be less than 10 High altitude adj...

Страница 29: ...ist in these adjustments are a CO2 or O2 Analyzer and a U Tube Manometer or other device capable of reading a pressure of 2 5 3 0 inches W C 0 62 0 75 kPa Start the adjustment process by checking the...

Страница 30: ...ore and after the valve and remove the valve Re install in reverse order Ensure o rings are properly installed for both inlet and outlet Turn on manual gas shutoff valve and 120 volt power and check a...

Страница 31: ...al gas valve on the heater 3 Disconnect and remove the wires conduit and sensors from all components that are attached to the inlet outlet header 4 Isolate the heat exchanger from the water supply 5 D...

Страница 32: ...esentative to discuss possible remedies 8 4 Short Cycling Water Heater Short cycling will generally occur only in combination space heating and water heating applications when the water heater is oper...

Страница 33: ...F3015 5F3015 5F3015 13 Cover Housing Pump 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 14 Cover Pipe Gas Manifold 5F3304 5F3304 10F3304 20F3304 20F3304 20F3304 20F3304 2 2 2 2 2 2 2 Internal Compo...

Страница 34: ...2018000 T2017400 T2018000 T2017400 45 Tile Bottom Center T2015900 T2015900 T2015900 T2015900 1 1 2 2 Gas Train Components See Figure 24 46 Blower A2111900 A2111900 A2111900 A2111900 A2111900 A2111900...

Страница 35: ...59 Low Water Cutoff optional E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 60 Gauge Temperature Pressure A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 62 Tee Adapter...

Страница 36: ...E0093200 E0093200 E0093200 79 Panel Mounting Limits Ignition Control 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 80 Panel Cover High Limit Ignition Control 5F7003 5F7003 5F7003 5F7003 5F7003 5F70...

Страница 37: ...Page 37 Brute Deluxe 500 2000 Install Operating Figure 23 Sheet Metal Components...

Страница 38: ...Page 38 Bradford White Corp Figure 24 Internal Components...

Страница 39: ...001800 1250 A2001800 1500 A2001900 1750 A2001900 2000 A2109700 Brute Deluxe Water Heater Size Pump p n Soft Water Normal Water Hard Water 500 A2001700 A2001700 A2001900 750 A2001700 A2001700 A2001900...

Страница 40: ...Bradford White Corporation reserves the right to change specifications components features or to discontinue products without notice 200 Lafayette St Middleville MI 49333 Warranty 800 531 2111 www Br...

Отзывы: