Brute Deluxe

 (

500-2000), Install & Operating

ferent types of readily available storage tanks. A pump 

draws water from the storage tank and pumps the water 

through the heater and back into the tank. Pump-mount-

ed units have a circulating pump built into the water 

heater. The pumps used are sized for the headloss 

through the heater, plus 30 feet (9.1m) of full-sized pip-

ing (same size as boiler outlet) and a normal number of 

fittings. Pumps used on pump-mounted unit are sized for 

soft/normal or hard water, so make sure a pump-mounted 

unit matches the water quality of the installation.

Pipe the outlet from the heater’s relief valve 

such that any discharge from the relief valve will be 

conducted to a suitable place for disposal when relief 

occurs. Do not reduce line size or install any valves in 

this line. The line must be installed to allow complete 

drainage of both the valve and the line.

Suggested piping diagrams are shown in 

Figures 11 

through 14

. These diagrams are meant only as a guide. 

Components required by local codes must be properly 

installed.

The minimum inlet water temperature for the Brute 

Deluxe is 120°F (49°C) to avoid condensing on the 

copper coils.

4B.2 Hot Water Supply Piping —

 

 Water Heater

Follow the tank manufacturer’s guidelines for 

completion of the hot water system connections.

NOTE: A listed temperature and pressure relief valve 

listed as complying with the Standard for Relief 

Valves and Automatic Gas Shutoff Devices for Hot 

Water Supply Systems (ANSI Z21.22 / CSA 4.4) of 

suitable discharge capacity must be installed in the 

separate storage tank system.

If the Brute Deluxe water heater is installed in 

a closed water supply system, such as one having a 

backflow preventer in the cold water supply line, the 

relief valve may discharge periodically, due to thermal 

expansion. Means (such as a properly-sized expansion 

tank) shall be provided to control thermal expansion. 

Contact the water supplier or local plumbing inspector 

on how to control this situation.

4B.3 Water Flow Requirements —

 

 Water Heater

In a water heating application (an open system), 

new water is constantly being introduced. With the 

new water comes a fresh supply of minerals that can 

be deposited on the unit’s heat exchanger. This is 

commonly known as scaling. The amount of minerals 

will depend upon the hardness of the water. Water can 

also be aggressive, and can erode metals, including 

copper, if the water is moved too quickly. The water 

flow requirements for the Brute Deluxe water heater are 

based upon the hardness of the water. The water flow is 

kept high enough to prevent scaling, but low enough to 

prevent tube erosion. For extremely soft or hard water, 

cupro-nickel tubes are available. Contact a Bradford 

White Representative if you have questions or concerns 

about water quality.

Pump-mounted water heaters can be ordered 

with standard pumps for soft or normal water or with 

pumps for hard water. The pumps used are sized for the 

headloss through the heater, plus 30 feet (9.1m) of full-

sized piping (same size as heater outlet) and a normal 

number of fittings. 

Table 9

 specifies water flow rates for water heaters, 

which will enable the user to size a pump. The headloss 

shown is for the heater only, and the user will need to add 

the headloss of the piping system to properly size the pump.

4B.4 Combined Water Heating (potable)  

 and Space Heating — Water Heater

NOTE: 

These systems are not allowed in the 

Commonwealth of Massachusetts.

Piping and components connected to this water 

heater for the space heating application shall be suitable 

for use with potable water.

Toxic chemicals, such as used for boiler treatment, 

shall not be introduced into the potable water used for 

space heating.

This water heater when used to supply potable 

water shall not be connected to any heating system or 

component(s) previously used with a non-potable water 

heating appliance.

When the system requires water for heating at 

temperatures higher than required for other uses, 

an anti-scald mixing or tempering valve shall be 

installed to temper the water for those uses in order 

to reduce scald hazard potential.

4B.5 Freeze Protection – Water Heater

Although Brute Deluxe water heaters are design-

certified for outdoor installations, such installations 

are not recommended in areas subject to freezing 

temperatures, unless proper precautions are taken.

Power outage, interruption of gas supply, failure 

of system components, activation of safety devices, etc., 

may prevent a heater from firing. 

Any time a heater is 

subjected to freezing conditions, and the heater is not 

able to fire, and/or the water is not able to circulate, 

there is a risk of freezing in the heater or in the pipes 

in the system. 

When water freezes, it expands. This 

can result in bursting of pipes in the system, or damage 

to the heater, which could result in leaking or flooding 

conditions.

Contact the local factory representative or Bradford 

White for additional information.

SECTION 5.

Electrical Connections 

Содержание BRUTE DELUXE BMT2H

Страница 1: ...r d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne to...

Страница 2: ...Heaters 4B 1 Water System Piping Water Heater 14 4B 2 Hot Water Supply Piping Water Heater 15 4B 3 Water Flow Requirements Water Heater 15 4B 4 Combined Water Heating potable and Space Heating Water H...

Страница 3: ...White factory or local factory representative with any issues or questions regarding this equipment Experience has shown that most operating issues are caused by improper installation The Brute Delux...

Страница 4: ...ry items are shipped in separate packages Verify receipt of all packages listed on the packing slip Inspect everything for damage immediately upon delivery and advise the carrier of any shortages or d...

Страница 5: ...ump is sized for 30 feet 9 1m of piping If the appliance must be installed with longer piping runs then larger diameter pipe or tubing shall be used Consult the factory for assistance Figure 1 Dimensi...

Страница 6: ...gure 2 Dimensional Data pump mounted models HORIZONTAL INTAKE AIR VENT COLLAR VENT PIPE PIPE MAX PIPE MAX NO SIDE WALL SIDE WALL SIZE SIZE DIAMETER DIAMETER LENGTH OF ELBOWS VENT COMBUSTION TERMINAL A...

Страница 7: ...ings shall communicate directly or by ducts with the outdoors or spaces that freely communicate with the outdoors When directly communicating with the outdoors or when communicating to the outdoors th...

Страница 8: ...he vent system must conform to the National Fuel Gas Code ANSI Z223 1 Latest Edition in the U S or in Canada to CSA B149 1 latest edition The vent system must be sized and installed for a Category I F...

Страница 9: ...appliances with condensing vents are not permitted to terminate above a public walkway or over an area where condensate or vapor could create a nuisance or hazard 3 Locate the vent terminal so that v...

Страница 10: ...t 3 feet 91 cm above if within 10 feet 3 m 6 feet 1 83 m horizontally Vent termination not allowed in this location Vent termination not allowed in this location for category IV appliances A vent shal...

Страница 11: ...ight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half in...

Страница 12: ...fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Foll...

Страница 13: ...ring any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 45kpa 9 The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during an...

Страница 14: ...he system To ensure a proper operating temperature leading to long boiler life a flow rate has been established based on the fluid temperature rise for this specific size boiler Pump mounted boilers c...

Страница 15: ...including copper if the water is moved too quickly The water flow requirements for the Brute Deluxe water heater are based upon the hardness of the water The water flow is kept high enough to prevent...

Страница 16: ...Page 16 Bradford White Corp Figure 6 Hydronic Piping Multiple Boilers Primary Secondary System Figure 7 Hydronic Piping Multiple Boilers Low Temperature System...

Страница 17: ...Page 17 Brute Deluxe 500 2000 Install Operating Figure 8 Hydronic Piping One Boiler Multi Temperature System Figure 9 Hydronic Piping Primary Secondary Reverse Return...

Страница 18: ...Page 18 Bradford White Corp Figure 10 Hydronic Piping Primary Secondary Reverse Return Low Temperature Figure 11 Water Heater Piping One Heater One Tank...

Страница 19: ...Page 19 Brute Deluxe 500 2000 Install Operating Figure 12 Water Heater Piping Multiple Heaters One Tank Figure 13 Water Heater Piping One Heater Multiple Tanks...

Страница 20: ...19 170 257 341 0 6 1 1 1 9 21 14 10 1250 68 68 90 3 8 3 8 6 3 31 31 24 257 257 341 1 2 1 2 1 9 17 17 13 1500 68 68 90 3 9 3 9 6 5 38 38 28 257 257 341 1 2 1 2 2 0 21 21 16 1750 68 68 90 4 0 4 0 6 7 4...

Страница 21: ...rk on or around the boiler may be standing on wet floors and could be electrocuted by an ungrounded boiler Single pole switches including those of safety controls and protective devices must not be wi...

Страница 22: ...BLOWER 1 LOW HIGH LOW HIGH K1 K2 K1 K2 F2 35 67 F2 35 67 F1 35 67 F1 35 67 K3 HSI 2 HSI 1 120 VAC DPDT MAIN POWER SWITCH S2 S2 35 67 35 67 L2 35 67 L2 35 67 BD 1 IGN S1 S1 35 67 35 67 35 67 L1 35 67 J...

Страница 23: ...Page 23 Brute Deluxe 500 2000 Install Operating Figure 19 Brute Deluxe 500 750 Connection Diagram...

Страница 24: ...Page 24 Bradford White Corp Figure 20 Brute Deluxe 1000 Connection Diagram...

Страница 25: ...K W L2 LOAD 1 1 2 3 4 5 6 7 8 9 10 10 lockout indicator T stat lockout indicator G Pressure Switch Gas Valve 24V Ground Remote Sense S1 L1 L2 S2 Fenwal F1 F2 lockout indicator T stat lockout indicator...

Страница 26: ...tiple boiler control BAS etc wire Stage 1 to the terminals marked Input Stage 1 and Stage 1 and wire Stage 2 to the terminals marked Input Stage 2 and Stage 2 The Local Remote selector switch above th...

Страница 27: ...ll bleeding devices and open make up water valve Allow system to fill slowly 2 If make up water pump is employed adjust pressure switch on pumping system to provide a minimum of 12 psi 81 8 kPa at the...

Страница 28: ...but with differing reductions in output At elevations higher than 7700 ft 2347 m the reduction in output will exceed 10 and at elevations below 7700 ft 2347 m it will be less than 10 High altitude adj...

Страница 29: ...ist in these adjustments are a CO2 or O2 Analyzer and a U Tube Manometer or other device capable of reading a pressure of 2 5 3 0 inches W C 0 62 0 75 kPa Start the adjustment process by checking the...

Страница 30: ...ore and after the valve and remove the valve Re install in reverse order Ensure o rings are properly installed for both inlet and outlet Turn on manual gas shutoff valve and 120 volt power and check a...

Страница 31: ...al gas valve on the heater 3 Disconnect and remove the wires conduit and sensors from all components that are attached to the inlet outlet header 4 Isolate the heat exchanger from the water supply 5 D...

Страница 32: ...esentative to discuss possible remedies 8 4 Short Cycling Water Heater Short cycling will generally occur only in combination space heating and water heating applications when the water heater is oper...

Страница 33: ...F3015 5F3015 5F3015 13 Cover Housing Pump 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 14 Cover Pipe Gas Manifold 5F3304 5F3304 10F3304 20F3304 20F3304 20F3304 20F3304 2 2 2 2 2 2 2 Internal Compo...

Страница 34: ...2018000 T2017400 T2018000 T2017400 45 Tile Bottom Center T2015900 T2015900 T2015900 T2015900 1 1 2 2 Gas Train Components See Figure 24 46 Blower A2111900 A2111900 A2111900 A2111900 A2111900 A2111900...

Страница 35: ...59 Low Water Cutoff optional E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 60 Gauge Temperature Pressure A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 62 Tee Adapter...

Страница 36: ...E0093200 E0093200 E0093200 79 Panel Mounting Limits Ignition Control 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 80 Panel Cover High Limit Ignition Control 5F7003 5F7003 5F7003 5F7003 5F7003 5F70...

Страница 37: ...Page 37 Brute Deluxe 500 2000 Install Operating Figure 23 Sheet Metal Components...

Страница 38: ...Page 38 Bradford White Corp Figure 24 Internal Components...

Страница 39: ...001800 1250 A2001800 1500 A2001900 1750 A2001900 2000 A2109700 Brute Deluxe Water Heater Size Pump p n Soft Water Normal Water Hard Water 500 A2001700 A2001700 A2001900 750 A2001700 A2001700 A2001900...

Страница 40: ...Bradford White Corporation reserves the right to change specifications components features or to discontinue products without notice 200 Lafayette St Middleville MI 49333 Warranty 800 531 2111 www Br...

Отзывы: