![Bradford White BRUTE DELUXE BMT2H Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/bradford-white/brute-deluxe-bmt2h/brute-deluxe-bmt2h_installation-and-operation-instructions-manual_2799424020.webp)
Page 20
Bradford White Corp
Figure 14. Water Heater Piping — Multiple Heaters, Multiple Tanks.
Table 9. Water Flow Requirements — BMT2V.
Unit
gpm
ft
Temp Rise °F
lpm
m
Temp Rise °C
Size
S
N
H
S
N
H
S N H
S N H
S N H
S N H
500
45
68
90
1.8
2.3
3.5
19 13 9
170 257 341 0.5 0.7 1.1
10 7 5
750
45
68
90
2.1
3.0
6.0
28 19 14
170 257 341 0.6 0.9 1.8
16 10 8
1000
45
68
90
2.3
3.6
6.1
38 25 19
170 257 341 0.6 1.1 1.9
21 14 10
1250
68
68
90
3.8
3.8
6.3
31 31 24
257 257 341 1.2 1.2 1.9
17 17 13
1500
68
68
90
3.9
3.9
6.5
38 38 28
257 257 341 1.2 1.2 2.0
21 21 16
1750
68
68
90
4.0
4.0
6.7
44 44 33
257 257 341 1.2 1.2 2.0
24 24 18
2000
112 112 112
10.0 10.0 10.0
30 30 30
424 424 424 3.0 3.0 3.0
17 17 17
NOTES:
S = soft water (1 to 7.5 grains hardness).
N = normal water (7.6 to 17 grains hardness).
H = hard water (more than 17 grains hardness).
gpm = gallons per minute; lpm = liters per minute; ft = headloss in feet; m = headloss in meters.
Headloss is for heater's heat exchanger only.
Содержание BRUTE DELUXE BMT2H
Страница 23: ...Page 23 Brute Deluxe 500 2000 Install Operating Figure 19 Brute Deluxe 500 750 Connection Diagram...
Страница 24: ...Page 24 Bradford White Corp Figure 20 Brute Deluxe 1000 Connection Diagram...
Страница 37: ...Page 37 Brute Deluxe 500 2000 Install Operating Figure 23 Sheet Metal Components...
Страница 38: ...Page 38 Bradford White Corp Figure 24 Internal Components...