Trouble Shooting

8.1  Resolving Lockouts

There are many causes of lockouts. The three most 

common causes are: (1) inadequate gas supply, (2) poor 

combustion, (3) ignitor failure.

1. 

Inadequate gas supply:

 Before proceeding, ensure 

that the gas supply has not been shutoff or the LP 

tank (LP boilers) is not empty. Then, restart the 

boiler and observe the operational cycle. After a 

15-second fan pre-purge, the ignitor will heat up 

for 20 seconds, and then the unit will light. If it 

does not, check the gas supply pressure to the ap-

pliance, after resetting the appliance and attempting 

another start-up. The gas pressure to the appliance 

must be above 5" W.C. (1.2kPa) throughout the 

entire start-up cycle. If it is not, correct the supply 

problem (check gas valves or supply piping). If the 

supply pressure is adequate, consult the factory for 

assistance.

2. 

Poor combustion:

 Poor combustion should be 

suspected if there is a strong flue gas odor. The 

odor may result from an improper gas/air ratio 

(high or low O

2

 or CO

2

). Brute Deluxe appliances 

operate best with 45% excess air (8% CO

2

 on 

natural gas, 9.2% CO

2

 on LP). Check the CO

2

 of 

the appliance and adjust if necessary.

3. 

Ignitor failure:

 If the boiler goes through a normal 

start cycle but combustion does not occur, ignitor 

failure should be suspected. Check the ignitor by 

unplugging the ignitor plug and measuring the 

ignitor resistance. It should be 50-80 ohms at room 

temperature. If the resistance is not 50-80 ohms, 

replace the ignitor. If the resistance is correct, reset 

the boiler and check for 120 VAC at the ignitor 

plug during the start cycle. If there is no voltage, 

replace the faulty ignitor wire harness or the 

ignition control.

8.2  Delayed Ignition — Possible Causes

A defective burner can cause a delayed ignition. If 

the gas supply pressure is proper and the gas valves are 

functioning properly, then burners should be inspected. 

There should be no distortion or perforations in the 

burners outside of the active burner port area. Replace if 

indicated.

8.3  Short Cycling — Boiler

Because the Brute Deluxe is a stage-fired boiler, 

and its input will decrease when there is a reduction 

in heating load, short cycling is greatly reduced. If 

the heating load drops below the minimum input of 

the boiler for an extended period, the boiler will have 

a tendency to short cycle. This can be a symptom 

of improper control strategy or setpoints, or a load 

distribution problem. Contact your Bradford White 

representative to discuss possible remedies.

8.4  Short Cycling — Water Heater

Short cycling will generally occur only in 

combination space heating and water heating applications 

when the water heater is operating in the space-heating 

mode. Because the Brute Deluxe is a stage-fired water 

heater and its input will reduce when there is a reduction 

in heating load, short cycling is greatly reduced. If the 

heating load drops below the minimum input of the water 

heater for an extended period, the water heater will have 

a tendency to short cycle. If short cycling is frequently 

experienced, regardless of the control’s attempt to limit it, 

the heating load should be redistributed to control it.

If short cycling occurs in a water heater application, it 

is probably caused by undersized piping between the water 

heater and the storage tank or by some other factor that 

restricts proper water flow through the water heater. The 

cause should be determined and corrected. 

8.5  High Gas Consumption

Appliances operating with an improper air/fuel ratio 

are very inefficient and consequently, have very high gas 

consumption. Because efficiency is high when the CO

2

 

is high (or O

2

 is low), appliances operating with low CO

2

 

or high O

2

 (especially LP appliances) consume more 

gas. Adjust the CO

2

 or O

2

 for optimum efficiency. If no 

combustion analyzing equipment (CO

2

 or O

2

) is available 

then a proper adjustment of the air/fuel ratio (CO

2

 or O

2

cannot be accomplished. However, by briefly sniffing 

the flue gases it is possible to determine if the CO

2

 or O

2

 

is within the proper range. No significant flue gas odor 

should be detected when combustion is proper. A strong 

piercing smell indicates poor combustion and generally 

a lean mixture - low CO

2

 or high O

. The CO

2

 should 

be 8% at high fire. To check the CO

2

, first verify that the 

supply gas pressure is within 5" to 13" w.c. (1.2 to 3.2 kPa) 

With the Brute Deluxe running with all stages firing, set 

the air box pressure to 1.5" w.c. (0.37 kPa) (as a starting 

point), by adjusting the air shutter(s) at the bottom of the 

fan(s). Check the CO

2

, and adjust the air shutters if further 

adjustment to the CO

2

 is needed. Sizes 1250 to 2000 have 

two blowers and two air chambers (boxes). The pressure 

of each air box must be equal when the final adjustment is 

made.

SECTION 9.

Replacement Parts

Only genuine Bradford White replacement parts should be used.

9.1  General Information

To order or purchase parts for the Bradford White 

Brute Deluxe, contact your nearest Bradford White 

dealer or distributor. If they cannot supply you with what 

you need, contact Customer Service 

(see back cover for 

address, telephone and fax numbers)

.

9.2  Parts List 

see next page.

Содержание BRUTE DELUXE BMT2H

Страница 1: ...r d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne to...

Страница 2: ...Heaters 4B 1 Water System Piping Water Heater 14 4B 2 Hot Water Supply Piping Water Heater 15 4B 3 Water Flow Requirements Water Heater 15 4B 4 Combined Water Heating potable and Space Heating Water H...

Страница 3: ...White factory or local factory representative with any issues or questions regarding this equipment Experience has shown that most operating issues are caused by improper installation The Brute Delux...

Страница 4: ...ry items are shipped in separate packages Verify receipt of all packages listed on the packing slip Inspect everything for damage immediately upon delivery and advise the carrier of any shortages or d...

Страница 5: ...ump is sized for 30 feet 9 1m of piping If the appliance must be installed with longer piping runs then larger diameter pipe or tubing shall be used Consult the factory for assistance Figure 1 Dimensi...

Страница 6: ...gure 2 Dimensional Data pump mounted models HORIZONTAL INTAKE AIR VENT COLLAR VENT PIPE PIPE MAX PIPE MAX NO SIDE WALL SIDE WALL SIZE SIZE DIAMETER DIAMETER LENGTH OF ELBOWS VENT COMBUSTION TERMINAL A...

Страница 7: ...ings shall communicate directly or by ducts with the outdoors or spaces that freely communicate with the outdoors When directly communicating with the outdoors or when communicating to the outdoors th...

Страница 8: ...he vent system must conform to the National Fuel Gas Code ANSI Z223 1 Latest Edition in the U S or in Canada to CSA B149 1 latest edition The vent system must be sized and installed for a Category I F...

Страница 9: ...appliances with condensing vents are not permitted to terminate above a public walkway or over an area where condensate or vapor could create a nuisance or hazard 3 Locate the vent terminal so that v...

Страница 10: ...t 3 feet 91 cm above if within 10 feet 3 m 6 feet 1 83 m horizontally Vent termination not allowed in this location Vent termination not allowed in this location for category IV appliances A vent shal...

Страница 11: ...ight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half in...

Страница 12: ...fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Foll...

Страница 13: ...ring any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 45kpa 9 The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during an...

Страница 14: ...he system To ensure a proper operating temperature leading to long boiler life a flow rate has been established based on the fluid temperature rise for this specific size boiler Pump mounted boilers c...

Страница 15: ...including copper if the water is moved too quickly The water flow requirements for the Brute Deluxe water heater are based upon the hardness of the water The water flow is kept high enough to prevent...

Страница 16: ...Page 16 Bradford White Corp Figure 6 Hydronic Piping Multiple Boilers Primary Secondary System Figure 7 Hydronic Piping Multiple Boilers Low Temperature System...

Страница 17: ...Page 17 Brute Deluxe 500 2000 Install Operating Figure 8 Hydronic Piping One Boiler Multi Temperature System Figure 9 Hydronic Piping Primary Secondary Reverse Return...

Страница 18: ...Page 18 Bradford White Corp Figure 10 Hydronic Piping Primary Secondary Reverse Return Low Temperature Figure 11 Water Heater Piping One Heater One Tank...

Страница 19: ...Page 19 Brute Deluxe 500 2000 Install Operating Figure 12 Water Heater Piping Multiple Heaters One Tank Figure 13 Water Heater Piping One Heater Multiple Tanks...

Страница 20: ...19 170 257 341 0 6 1 1 1 9 21 14 10 1250 68 68 90 3 8 3 8 6 3 31 31 24 257 257 341 1 2 1 2 1 9 17 17 13 1500 68 68 90 3 9 3 9 6 5 38 38 28 257 257 341 1 2 1 2 2 0 21 21 16 1750 68 68 90 4 0 4 0 6 7 4...

Страница 21: ...rk on or around the boiler may be standing on wet floors and could be electrocuted by an ungrounded boiler Single pole switches including those of safety controls and protective devices must not be wi...

Страница 22: ...BLOWER 1 LOW HIGH LOW HIGH K1 K2 K1 K2 F2 35 67 F2 35 67 F1 35 67 F1 35 67 K3 HSI 2 HSI 1 120 VAC DPDT MAIN POWER SWITCH S2 S2 35 67 35 67 L2 35 67 L2 35 67 BD 1 IGN S1 S1 35 67 35 67 35 67 L1 35 67 J...

Страница 23: ...Page 23 Brute Deluxe 500 2000 Install Operating Figure 19 Brute Deluxe 500 750 Connection Diagram...

Страница 24: ...Page 24 Bradford White Corp Figure 20 Brute Deluxe 1000 Connection Diagram...

Страница 25: ...K W L2 LOAD 1 1 2 3 4 5 6 7 8 9 10 10 lockout indicator T stat lockout indicator G Pressure Switch Gas Valve 24V Ground Remote Sense S1 L1 L2 S2 Fenwal F1 F2 lockout indicator T stat lockout indicator...

Страница 26: ...tiple boiler control BAS etc wire Stage 1 to the terminals marked Input Stage 1 and Stage 1 and wire Stage 2 to the terminals marked Input Stage 2 and Stage 2 The Local Remote selector switch above th...

Страница 27: ...ll bleeding devices and open make up water valve Allow system to fill slowly 2 If make up water pump is employed adjust pressure switch on pumping system to provide a minimum of 12 psi 81 8 kPa at the...

Страница 28: ...but with differing reductions in output At elevations higher than 7700 ft 2347 m the reduction in output will exceed 10 and at elevations below 7700 ft 2347 m it will be less than 10 High altitude adj...

Страница 29: ...ist in these adjustments are a CO2 or O2 Analyzer and a U Tube Manometer or other device capable of reading a pressure of 2 5 3 0 inches W C 0 62 0 75 kPa Start the adjustment process by checking the...

Страница 30: ...ore and after the valve and remove the valve Re install in reverse order Ensure o rings are properly installed for both inlet and outlet Turn on manual gas shutoff valve and 120 volt power and check a...

Страница 31: ...al gas valve on the heater 3 Disconnect and remove the wires conduit and sensors from all components that are attached to the inlet outlet header 4 Isolate the heat exchanger from the water supply 5 D...

Страница 32: ...esentative to discuss possible remedies 8 4 Short Cycling Water Heater Short cycling will generally occur only in combination space heating and water heating applications when the water heater is oper...

Страница 33: ...F3015 5F3015 5F3015 13 Cover Housing Pump 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 14 Cover Pipe Gas Manifold 5F3304 5F3304 10F3304 20F3304 20F3304 20F3304 20F3304 2 2 2 2 2 2 2 Internal Compo...

Страница 34: ...2018000 T2017400 T2018000 T2017400 45 Tile Bottom Center T2015900 T2015900 T2015900 T2015900 1 1 2 2 Gas Train Components See Figure 24 46 Blower A2111900 A2111900 A2111900 A2111900 A2111900 A2111900...

Страница 35: ...59 Low Water Cutoff optional E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 60 Gauge Temperature Pressure A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 62 Tee Adapter...

Страница 36: ...E0093200 E0093200 E0093200 79 Panel Mounting Limits Ignition Control 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 80 Panel Cover High Limit Ignition Control 5F7003 5F7003 5F7003 5F7003 5F7003 5F70...

Страница 37: ...Page 37 Brute Deluxe 500 2000 Install Operating Figure 23 Sheet Metal Components...

Страница 38: ...Page 38 Bradford White Corp Figure 24 Internal Components...

Страница 39: ...001800 1250 A2001800 1500 A2001900 1750 A2001900 2000 A2109700 Brute Deluxe Water Heater Size Pump p n Soft Water Normal Water Hard Water 500 A2001700 A2001700 A2001900 750 A2001700 A2001700 A2001900...

Страница 40: ...Bradford White Corporation reserves the right to change specifications components features or to discontinue products without notice 200 Lafayette St Middleville MI 49333 Warranty 800 531 2111 www Br...

Отзывы: