38/52 Commissioning
Bosch Rexroth AG
, VT-MRMA1-1, RE 30214-B/03.2019
8.1.3 Measuring signal and measuring point selector switch
Test jack v is provided for checking various command and actual values and ramp
times (for changing the measuring point switch over, use a screwdriver with a blade
width of approx. 2.5 mm).
Measurements on the amplifier module may only be taken using measuring
instruments with an internal resistance of (Ri) > 100 kΩ!
Fig. 17: Measuring point selector switch
Test jack:
0 to +10 V ±2 %
I
max
= 2 mA
Depending on the selected measuring point selector switch position (see table
below), a certain measured signal can be output at test jack v:
Table 32: Measuring signals
Switch position
Measuring point
Measuring signal at test jack v
0
Pressure command value
wP
0 % = 0 V
100 % = 10 V
1
Actual pressure value
xP
0 % = 0 V
100 % = 10 V
2
Valve position command
value
wS
0 % = 0 V
100 % = 10 V
3
Actual valve position value
xs
0 % = 0 V
100 % = 10 V
4
Ramp times “up”
t <
10 mV to 10 V
5
Ramp time “down”
t >
10 mV to 10 V
Fixed potentials for orientation
6
No function
0 V
7
No function
< -10 V
8
No function
< -10 V
9
No function
< -10 V
8.1.4 LEDs
A total of 3 LEDs on the front panel of the amplifier module provide information
about the states of the amplifier module:
• Readiness for operation (green)
• Cable breaks of the pressure transducer cables (red)
• Enable for position controller and output stage (yellow)
Measuring
signal
Load zero
Measuring point selector switch (position 0 - 5 valid)
Technical data
Measuring point selector