7.10.3 Actual Pressure Monitoring
Code
Name
Setting range
Default
Min. Attri.
F4.00 Protection function configuration
word
0...15
Bit0: Pressure sensor fail-
ure (PSF)
Bit1: Actual pressure moni-
toring
Bit2: p/Q max. command
limit
Bit3: Oil changing detection
0
-
Run
F4.15 Maximum system pressure (warn-
ing)
0.0...[F4.16] bar
500.0
0.1
Stop
F4.16 Maximum pump pressure (error)
[F4.15]...4,000.0 bar
1,000.0 0.1
Stop
F4.17 Maximum system pressure warning
time delay
0.0...6000.0 s
0.0
0.1
Run
F4.18 Maximum pump pressure error time
delay
0.0...6000.0 s
0.0
0.1
Run
Tab. 7-21: Parameter list of pressure over limit detection
The detection of pressure feedback can be activated via bit1 of F4.00.
F4.15: When the feedback pressure goes beyond [F4.15] bar for [F4.17] s, the
warning (d0.88 = 1) will be triggered for the pressure feedback surpassing the
maximum system allowed pressure.
F4.16: When the feedback pressure goes beyond [F4.16] bar for [F4.18] s, the
failure (d0.89 = 1) will be triggered for the pressure feedback surpassing the
pump limit pressure, and then drive stops.
Fig. 7-21: F4.15 maximum system pressure warning
Bosch Rexroth AG
Block Diagram of Main Functions
FcP 5020
48/83
DOK-RCON03-FCP5020****-QU04-EN-P