6.2 Analog Input
This section shows how analog input can be configured. The following figure is
an example for analog input AI2, which has been assigned to pressure feedback.
The configuration for AI1, EAI and EAI2 is similar to AI2, only with different pa-
rameters shown in the table below.
Fig. 6-2: Example with analog input AI2 assigned to pressure feedback
Code
Name
Setting Range
Default
Min.
Attri.
E1.35 AI1 input mode
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2...10 V
2
-
Run
E1.40 AI2 input mode
1
-
Run
H8.05 EAI input mode
0...4 (same as E1.35)
5: -10V...10V
0
-
Stop
H8.30 EAI2 input mode
0: 0...20 mA
1: 4...20 mA
2: 0…10 V
3: 0…5 V
4: 2...10 V
5: -10...10 V
0
-
Stop
FcP 5020
Bosch Rexroth AG
Electric Connection
DOK-RCON03-FCP5020****-QU04-EN-P
11/83