F3.00 p/Q parameter selection source
0: Depend on the value of
F3.01
1: Digital input (F3.01
shows status)
2: Communication
0
-
Stop
F3.01 p/Q parameter digital selection
0: Parameter group 0
1: Parameter group 1
0
-
Run
Tab. 7-8: Parameter list of p/Q parameter selection
Fig. 7-9: p/Q parameter group selection
If the two points / double pump function is active (see F4.03 bit3), the p/Q pa-
rameter selection function shown in the figure above will be deactivated, and
the p/Q controller parameter sets can only be switched according to the pump
switching logic.
Code
Name
Setting range
Default
Min.
Attri.
F3.12 Proportional gain [0]
0.00...500.00 rpm/bar
8.00
0.01
Run
Tab. 7-9: Parameter list of p/Q PID controller proportional gain setting
The parameter F3.12 is used to set the proportional gain of p/Q PID controller.
Pressure loop response is faster with a higher proportional gain. But excessively
high proportional gain can cause pressure over modulation and pressure oscilla-
tion.