6.3 Analog Output
This section shows how analog output can be configured. The following figure is
an example for analog output AO1. The configuration for EAO is similar to AO1,
only with different parameters shown in the table below.
Fig. 6-3: Example with analog output AO1
Code
Name
Setting Range
Default
Min.
Attri.
E2.25 AO1 output mode
0: 0...10 V
1: 0...20 mA
1
-
Run
E2.27 AO1 gain setting
0.00...10.00
1.00
0.00
Run
F2.04
Pressure command corre-
sponding to 5V, 10V or
20mA
0.1...1,000.0 bar
10.0
0.1
Stop
F2.06
Pressure feedback corre-
sponding to 5V, 10V or
20mA
0.1...1,000.0 bar
100.0
0.1
Stop
F2.08 Flow command correspond-
ing to 5V, 10V or 20mA
1...5,000 rpm
400
1
Stop