Parameter number
Parameter description
IDN/S-0-0021
IDN list of invalid operation data for CP2
Description
List of all IDN parameters with an invalid
operation date for switching from CP2 to
CP3
Data type, length List (IDN), variable
Write-protection
always
Default value
–
IDN/S-0-0022
IDN list of invalid operation data for CP3
Description
List of all IDN parameters with an invalid
operation date for switching from CP3 to
CP4
Data type, length List (IDN), variable
Write-protection
always
Default value
–
Tab. 9-16:
Function group control (FG_Control)
Parameter number
Parameter description
IDN/S-0-1028
Error counter MST-P/S
Description
Current error counter for failed MSTs
(MDT0 telegrams) on port 1 or port 2 or the
ports that correspond to the primary or
secondary port of the Sercos master
Data type, length Integer (decimal), 16 bits
Write-protection
always
Default value
–
IDN/S-0-1031
Error counter MST-P/S
Description
This parameter allows the assignment of
internal signals for test pins of the commu‐
nication hardware
Data type, length Integer (binary), 16 bit
Write-protection
Never
Default value
–
IDN/S-0-1044
Device control (C-DEV)
Description
Control word of the Sercos slave. The con‐
trol word C-DEV is used for the visual iden‐
tification (LED) of the device and for the
topology control. The C-DEV is cyclically
transferred in the MDT telegram
Data type, length Integer (binary), 16 bit
Write-protection
always
Default value
–
DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
Bosch Rexroth AG
75/139
Sercos