Sercos services
SVC, RTC, CC, IP
Sercos profiles
GDP_Basic, SCP_VarCfg, SCP_Sync,
SCP_Diag, SCP_WD, SCP_NRT,
FSP_IO
Sercos communication hardware
SERCON100S V04 R08
Tab. 4-8:
Field bus
4.11.3
Module Power Supply
Connection type
M12 connector, A-coded, 4-pin
Protection function
Reverse polarity protection for U
LS
+ U
A
Short-circuit protection of sensor supply
Current-carrying capacity of supply con‐
nections
Maximum: 8 A (U
LS
: 4 A, U
A
: 4 A)
Supply voltage
Logic and sensor voltage U
LS
Actuator voltage U
A
①
DC 24 V (-25 % … +30 %)
DC 24 V (-25 % … +30 %)
Supply current
Logic and sensor current I
LS
Actuator current I
A
Typically 140 mA + sensor technology
(max. 400 mA)
5 mA
①
Also required to conduct supply voltage
Tab. 4-9:
Module supply
4.11.4
Communication
S-BUS connection
Shielded M12 connector, B-coded, 5-pin
Number of expandable modules
Max. 64
Clearance between 2 modules
Max. 20 m
Total station expansion
Max. 200 m
Tab. 4-10:
Communication
4.11.5
Digital Inputs
Number of inputs
8
Connection type
M8 male connectors, 3-pin
Termination technique
2- to 3-wire
Input filter
Hardware ≤ 10μs; can be parameterized
using software depending on the opera‐
tion mode
Input characteristic curve
Type 1, acc. to IEC 61131-2
Signal voltage 0
-30 V … +5 V DC
Signal voltage 1
+15 V … +30 V DC
Input circuit
Positive switching
Input voltage
24 V DC (-30 V DC < U
IN
< +30 V DC)
Bosch Rexroth AG
DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
24/139
Device Description of Field Bus Coupler
Содержание Rexroth IndraControl S67 Series
Страница 106: ...Bosch Rexroth AG DOK CONTRL S67S3BKDI8 AP03 EN P Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs M8 104 139 ...
Страница 134: ...Bosch Rexroth AG DOK CONTRL S67S3BKDI8 AP03 EN P Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs M8 132 139 ...
Страница 136: ...Bosch Rexroth AG DOK CONTRL S67S3BKDI8 AP03 EN P Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs M8 134 139 ...