Fig.8-7: S-curve
– Stage ① is defined by [b1.23] with percent of acceleration time.
– Stage ④ is defined by [b1.23] with percent of deceleration time.
– Stage ③ is defined by [b1.24] with percent of acceleration time.
– Stage ⑥ is defined by [b1.24] with percent of deceleration time.
b1.25 ~ b1.29
Reserved
b1.30
Starting mode
Setting range
0 ~ 2
Minimum unit
1
Factory default 0
b1.31
Starting frequency
Setting range
0.00 ~ 50.00 Hz
Minimum unit
0.01 Hz
Factory default 0.05 Hz
b1.32
Starting frequency holding time
Setting range
0.0 ~ 20.0s
Minimum unit
0.1s
Factory default 0.1s
b1.33
Starting DC braking time
Setting range
0.0 ~ 20.0s (0.0 represents no action of starting DC braking)
Minimum unit
0.1s
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
68/235
Содержание Rexroth EFC 3600
Страница 6: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 IV 235 ...
Страница 232: ...230 235 ...
Страница 236: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 234 235 ...
Страница 237: ...Notes DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 Bosch Rexroth AG ...