5.3
EFC 3600 Mounting
The equipment must be sufficiently ventilated to avoid overheating. The recommended
minimum clearances between the frequency converter and adjacent items, which may
disturb the free flow of air, are given below.
Fig.5-3: EFC 3600 mounting
● EFC 3600 must be vertically installed.
● EFC 3600 has no side ventilation hole, which enables parallel mounting
of EFC 3600 with zero distance.
● If one frequency converter is arranged above another, make sure that
the upper limit of air temperature into the inlet is not exceeded (See
fig.
10-1 "General technical data" on page 141
).
● A baffle plate is recommended between the frequency converters to
prevent the rising hot air being drawn into the upper frequency convert‐
er.
Bosch Rexroth AG
Mounting and Installation
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
26/235