Frequency detection
Function
code
Name
Setting range
Min.
unit
Factory
default
Attribute
E1.04
Frequency arriving
at detection width
0.00 ~ 400.0
0.01
2.50
RUN/STOP
E1.05
Frequency detection
level FDT1
0.00 ~ 400.0
0.01
50.00
RUN/STOP
E1.06
Frequency detection
level FDT1 width
0.00 ~ [E1.05]
0.01
1.00
RUN/STOP
E1.07
Frequency detection
level FDT2
0.00 ~ 400.0
0.01
25.00
RUN/STOP
E1.08
Frequency detection
level FDT2 width
0.00 ~ [E1.07]
0.01
1.00
RUN/STOP
Overload pre-protection
Function
code
Name
Setting range
Min.
unit
Factory
default Attribute
E1.09
Frequency converter
overload pre-warning
level setting
20.0 % ~ 200.0 %
(Rated frequency
converter current)
0.1 % 110.0 % STOP
E1.10 Motor overload pre-warn‐
ing level setting
100.0 % ~ 250.0 %
(Rated motor current)
0.1 % 100.0 % RUN/
STOP
E1.11
Frequency converter
overload pre-warning
delay
0.0 ~ 20.0
0.1
2.0
STOP
E1.12
Motor overload
pre-warning delay
0.0 ~ 20.0
0.1
2.0
RUN/
STOP
Bosch Rexroth AG
Appendix
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
214/235
Содержание Rexroth EFC 3600
Страница 6: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 IV 235 ...
Страница 232: ...230 235 ...
Страница 236: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 234 235 ...
Страница 237: ...Notes DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 Bosch Rexroth AG ...
Страница 238: ...ООО Комфорт Компани 03038 г Киев Украина ул Н Гринченко 4 тел 38 044 362 3676 info comfort co com comfort co com ...