Skip frequency
Function code
Name
Setting range
Min.
unit
Factory
default Attribute
S3.05
Skip frequency 1
0.00 ~ [b1.06]
0.01 Hz 0.00 Hz
STOP
S3.06
Skip frequency 2
0.00 ~ [b1.06]
0.01 Hz 0.00 Hz
STOP
S3.07
Skip frequency 3
0.00 ~ [b1.06]
0.01 Hz 0.00 Hz
STOP
S3.08
Skip frequency range 0.00 ~ 30.00 Hz 0.01 Hz 0.00 Hz
STOP
S3.09
Skip frequency
window acceleration
factor
1~100
1
1
STOP
S3.10 ~ S3.14 Reserved
–
–
–
–
Restarting after power fault
Function code
Name
Setting
range
Min.
unit
Factory
default Attribute
S3.15
Restarting after power fault
0: Prohibited
1: Allowed
1
0
STOP
S3.16
Waiting time for restarting
after power fault
0.0 ~ 10.0s
0.1s
1.0s
STOP
S3.17 ~ S3.19 Reserved
–
–
–
–
Brake chopper control
Function code
Name
Setting range
Min.
unit
Factory
default Attribute
S3.20
Brake chopper
action point
200 V class: 300 ~ 390 V
400 V class: 600 ~ 885 V
1 V
390 V
885 V
STOP
S3.21
Braking ratio
1 % ~ 100 %
1 %
100 %
STOP
S3.22 ~ S3.29 Reserved
–
–
–
–
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Appendix
207/235
Содержание Rexroth EFC 3600
Страница 6: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 IV 235 ...
Страница 232: ...230 235 ...
Страница 236: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 234 235 ...
Страница 237: ...Notes DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 Bosch Rexroth AG ...
Страница 238: ...ООО Комфорт Компани 03038 г Киев Украина ул Н Гринченко 4 тел 38 044 362 3676 info comfort co com comfort co com ...