About this product | Automax 100 | Extension module TS-AC E2-M3-1X
25/94
Bosch Rexroth AG | 05.2021 | DOK-SUPPL*-TS-AC E2-M3-ITRS-EN-P
Rotary coding switch
By means of the rotary coding switch, address assignments and other functions can be
configured.
After the switch position is changed, the bus coupler must be restarted for the new switch
position to take effect.
Rotary coding switch
The code is a sum of S1 x 10 plus S2 x 1. The figure illustrates: Code 77 (7 x 10 + 7).
The following table provides an overview of the available functions.
Rotary coding switch functions
S1
S2
Code
Function
0
0
00
Remove access (default)
0..5
0..9
01..50
Manual address assignment
5..15
0..9
51..159
DHCP name assignment
0
A
0A
Static address
0
E
0E
Reset IP parameters
1
A
1A
Activate plug-and-play mode
1
B
1B
Deactivate plug-and-play mode
12
C
12C
Reset to factory settings
Reset-push button
The reset push button is located under the upper inscription label of the bus coupler.
Inscription label
Reset-push button
Bus coupler reset push button