5-18
Instructions for Use
Rexroth Diax 04 HVE/HVR
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
HVE02/HVE03
HVE04
Type
screw terminal
screw terminal
Number of poles
2
2
Type of design
screw terminal for ring
cable lug M5
multi-core with
connector sleeve or
single-core
Cross section [mm
2
]
10...25
16...50
Tightening torque
2,5...3,0
6...8
Fig. 5-49:
Design
X13
2L+
device internal
device external
1L+
optional
choke
GLD xx
AP_X13.fh7
Fig. 5-50: Terminal assignment
•
HVE02/HVE03: with jumper from 1L+ to 2L+
•
HVE04: without jumper
(if the optional choke is not required, a jumper has to be laid from 1L+
to 2L+; line cross section: see below)
max. voltage with reference to L-
DC 900 V
voltage with reference to ground
provided mains voltage
max. continuous current
•
HVE02/03: 70 A
•
HVE04: 150 A
Fig. 5-51: Load capacity
line length
max. 10 m
line cross section
not smaller than cross section of
supply feeder;
minimum cross section: see data
under "Design"
line routing
twisted
dielectric strength of single strand
against ground
≥
750 V
(e.g.: strand type – H07)
Fig. 5-52: Line 1L+ and 2L+
Design
Terminal assignment
Condition as supplied
Load capacity
Line 1L+ and 2L+ to choke