5-14
Instructions for Use
Rexroth Diax 04 HVE/HVR
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
Power supply in order (UD)
The UD contact acknowledges that the power supply is in working order.
It opens in the event of the following faults:
•
mains
fault
•
DC bus voltage is smaller than the permissible minimum value
(HVR: 680 V, HVE: 80% of U
Netz
)
•
when switching off K1
If the installation requires that the drives be shutdown with position control
in the event of a mains fault, then the installation control must evaluate
the UD contact and shut down the drives in a controlled fashion.
Pre-warning (VW)
The pre-warning contact is opened, if the cooling unit temperature in the
power supply unit is too high or a critical value is reached in an additional
component. The mains contactor in the power supply unit interrupts the
power supply after 30 seconds and the Bb1 contact opens.
Note:
If the installation requires that the drives are shut down in a
position controlled fashion if there is a fault in the unit, then the
drives must be shutdown within 30 seconds.
Bleeder pre-warning contact (BVW)
The bleeder pre-warning contact only exists in the HVE power supply
units. The bleeder pre-warning contact opens if continuous regenerated
power exceeds 80% of the continuous bleeder power. If the bleeder
power continues to rise, then the mains contactor stops the HVE power
supply unit and the Bb1 contact opens.
X8, Control voltage supply
hve_X8.fh7
2u2
2v2
2w2
2u1
2v1
2w1
12
1
32
3
1
2
3
4
5
6
hvr_X8.fh7
2u1
2v1
2w1
frei
123
4
1
2
3
4
HVE
HVR
Fig. 5-38: Terminal X8
Type
Number of poles
Type of design
screw terminal
1 x 4 for HVR
1 x 6 for HVE
bushing at connector
Fig. 5-39:
Design
Terminal X8
Design