Rexroth Diax 04 HVE/HVR
Ratings and Dimensions
3-3
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
Description
Symbol
Unit
HVR02.2-W010N HVR02.2-W025N HVR03.2-W045N
pollution degree (UL)
Use in a pollution degree 2 environment
maximum ambient temperature with
nominal data (UL)
T
amax
°C
45
maximum ambient temperature with
reduced nominal data (UL)
T
amax_red
°C
55
Weight
m
kg
21
21
31
Device height (UL)
1)
H
mm
498
Device depth (UL)
2)
T
mm
308
Device width (UL)
3)
B
mm
175
175
250
minimum distance on the top of the
device
4)
d
top
mm
300
minimum distance on the bottom of the
device
5)
d
bot
mm
100
rated control voltage input (UL)
6)
U
N3
V
3 x 380…480
rated power consumption control voltage
input without holding brake, without
control section at U
N3
= DC 24 V (UL)
7)
P
N3
W
500
short circuit current rating, SCCR,
symmetrical amperes (UL)
8)
I
SCCR
A rms
42000
rated input voltage, power (UL)
9)
V
3 x 380…480
tolerance rated input voltage (UL)
%
±10
input number of phases (UL)
3
input frequency (UL)
f
LN
Hz
50…60
tolerance input frequency (UL)
Hz
±2
maximum input current (UL)
10)
I
L_cont
A
18
45
80
branch circuit protection fuse (UL)
11)
25
70
100
field wiring material (UL)
12)
Use 60/75 °C copper wire only, use class 1 wire only or
equivalent
required wire size section according UL
508 A (internal wiring); at I
L_cont
(UL)
13)
A
LN
AWG
6
6
2
maximum output voltage (UL)
U
out
V
750 dc
maximum output current (UL)
I
out_max
A
13
33
60
power dissipation at continuous current
I
out_cont
and continuous DC bus power
P
DC_cont
respectively (UL)
14)
P
Diss_cont
W
450
900
1500
1) 2) 3)
housing dimension; see related dimension sheet also
4) 5)
see fig. "Air intake and air outlet of drive controller"
6)
observe supply voltage for motor holding brakes
7)
find value for control section in project planning manual
8)
Suitable for use on a circuit capable of delivering not more than this
SCCR value, 600 V AC or less. The drive series shall be used with
listed AC input line fuses or listed circuit breakers specified in this
documentation.
9)
HDS, HDD, HZB, HZK: DC bus L+, L-; HVE/HVR: mains input
U, V, W
10)
at P
DC_cont
11)
class J branch circuit fuse
12)
find value for tightening torque in project planning manual, electrical
terminals
13)
copper wire; PVC-insulation (conductor temperature 90 °C); Table
13.5.1; Ta
≤
40 °C
14)
plus dissipation of braking resistor
Abb. 3-3:
UL ratings and dimensions