5-12
Instructions for Use
Rexroth Diax 04 HVE/HVR
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
Note:
The indicated voltages have to refer to potential ground.
"Acknowledge power ON"
At output acknowledge power ON it can be queried as to whether the
mains contactor in the supply unit is on or not. The contact is closed if the
mains contactor is on. It can be used as a precondition for the drive
enable signal.
"Acknowledge power OFF"
At output acknowledge power OFF it can be queried as to whether the
mains contactor in the supply unit has dropped off or not. If it has, then
the contact is closed. This can be used as a precondition to enable the
safety door lock.
There is restricted guidance between the acknowledge power OFF
contact and the main contacts of the mains contactor in the power supply
unit.
On the HVE power supply unit, there are two brake contacts labeled as
"Acknowledge power Off" led to the outside of the unit.
X7, Ready-to-operate and other messages
hve_X7.fh7
1
2
3
4
5
6
7
8
12345678
Bb1
Bb1
UD
UD
TVW
TVW
BVW
BVW
hzs_X7.fh7
1
2
3
4
5
6
7
8
12345678
Bb1
Bb1
UD
UD
TVW
TVW
n.c.
n.c.
hvr_X7.fh7
1
2
3
4
5
6
123456
Bb1
Bb1
UD
UD
TVW
TVW
HVE
HZS
HVR
Fig. 5-33:
Terminal X7
Type
Number of poles
Type of design
screw terminal
1 x 6 for HVR
1 x 8 for HVE
bushing at connector
Fig. 5-34:
Design
Cross section
single-core
[mm²]
Cross section
multic-core
[mm²]
Wire size
in AWG
gauge No.:
0,2...2,5
0,25 - 2,5
24...12
Fig. 5-35:
Connection cross section
0,5 Nm
Terminal X7
Design
Connection cross section
Tightening torque