
64
|
Flue gas test
Greenstar FS
6 720 810 590 (2015/05)
12.4
Dynamic gas pressure test
▶ Switch the appliance OFF and close the gas shut-off valve.
▶ Loosen the screw in the test port for gas inlet pressure
(
Fig. 74, [1]) and connect a pressure gauge (
Fig. 75).
Fig. 75 Dynamic gas pressure test port
▶ Turn on the gas cock and switch the appliance ON.
▶ Press and hold the emissions test button
until it lights up.
The display shows the supply temperature alternating with
=
maximum set output in heating mode
.
▶ Briefly press the emissions test button
.
The display shows the supply temperature in alternation with
=
maximum nominal output
.
▶ Check the required inlet gas pressure according to table 23.
▶ Press the emissions test button
until the light goes out.
The display returns to the supply temperature.
▶ Switch the appliance OFF, turn off the gas cock, remove the pressure
gauge and tighten the screw in the test port for gas inlet pressure.
▶ Reinstall the cover.
13
Flue gas test
13.1
Emissions test button
The following appliance outputs can be selected by pressing the
emissions test button
until it lights up:
Fig. 76 Press the emissions test button
•
= Maximum set output in heating mode (à Maximum heating
output, page 57)
•
= Maximum nominal output
•
= Minimum nominal output
13.2
Measuring CO content of flue gas
Use a multiport flue gas probe for the measurements.
▶ Open one of the flue gas test ports (
Fig. 71).
▶ Insert the flue gas probe approx. 2-3/4 inches (70 mm) into the test
port and seal around it.
▶ Press the emissions test button to select
=
maximum nominal
output
.
▶ Measure the CO levels.
▶ Repeatedly press the emissions test button
until the light goes
out.
The display returns to the supply temperature.
▶ Remove flue gas probe and close the flue gas test port properly.
Gas type
Nominal
pressure
" W.C. (mbar)
Permissible pressure range
for maximum nominal output
" W.C. (mbar)
NG
7 (17.4)
3.5-10.5 (8.7-26.1)
LPG (propane)
11 (27.4)
8-13 (19.9-32.3)
Table 23 Inlet gas pressure
Do not operate the appliance if the measured value is
below or above these values. Determine the cause and
eliminate the fault. If this is not possible, block the
appliance on the gas side and notify the gas supplier.
6 720 614 090-34.2O
You have 15 minutes to complete the tests. After that,
the appliance returns to default mode.
DANGER:
Risk of flue gas poisoning.
The CO level in the flue gas must be below 200 ppm (air
free).
▶ If 9.4 Vol.%
1)
CO
2
and a CO level under 200 ppm (af)
can not be achieved due to the gas supplied, use a
lower CO
2
level with CO emissions under 200 ppm
(af) instead.
1) 9.4 Vol.% with NG and 11.0 Vol.% with LPG (propane)
max
1
2
3
4
5
6
eco
reset
6 720 641 933-51.1O
max
1
2
3
4
e
6
min
Содержание KBR16-3
Страница 81: ...Spare parts 81 6 720 810 590 2015 05 Greenstar FS Fig 94 Group 1 Sheet metal Greenstar 6720810590 73 1Wo ...
Страница 85: ...Spare parts 85 6 720 810 590 2015 05 Greenstar FS Fig 96 Group 3 Gas valve Greenstar 6720810590 75 1Wo ...
Страница 91: ...Spare parts 91 6 720 810 590 2015 05 Greenstar FS Fig 99 Group 6 Control box Greenstar 6720810590 78 1Wo ...
Страница 98: ...98 Greenstar FS 6 720 810 590 2015 05 Notes ...
Страница 99: ... 99 6 720 810 590 2015 05 Greenstar FS Notes ...