Installation
|
37
6 720 810 590 (2015/05)
Greenstar FS
Fig. 29 Installing the concentric vent adaptor
[1]
Concentric vent adaptor
[2]
Screws
[3]
Combustion air test port
[4]
Flue gas test port
6.8.1
Installation of the exhaust and air intake system
Direct vent installations (sealed combustion)
For direct vent applications all applicable items below must be met.
Fig. 30 Vent & combustion air pipe position of a sealed combustion
system
[1]
Intake
[2]
Exhaust
X
At least 1 foot (305 mm)
The termination shall terminate at least 1 foot (305 mm) below, 1 foot
(305 mm) horizontally from or 1 foot (305 mm) above any door,
window or gravity air inlet into any building (
fig. 31 [2], [X
1
], [X
3
],
page 40).
If multiple boilers are installed in a row, allow at least 1 foot (305 mm)
clearance between the vent termination of one and the combustion air
intake of the other.
DANGER:
Carbon Monoxide poisoning
Improper venting of the Greenstar boiler can result in
excessive levels of carbon monoxide which can result in
severe personal injury or death.
▶ The boiler must be vented in accordance with the
“Venting of Equipment” section of the latest edition
of ANSI Z 223.1 / NFPA 54 Natural Fuel Gas Code
and/or the “Venting systems and air supply for
appliances”section of the latest version of CAN/CGA
B149.1 Natural Gas and Propane Installation Code in
Canada and in accordance with all applicable local
building codes.
DANGER:
Flue connections
Incorrectly fitted flue connections can lead to carbon
monoxide escaping into the boiler room.
▶ Ensure that the flue pipes and seals are not
damaged.
▶ Use only sealing compounds (primer and glue)
approved with the vent material.
▶ Never install a barometric or a thermally controlled
vent damper with this boiler.
▶ Connect only one boiler to each flue system.
▶ Do not route the flue system piping through or inside
another duct that is used for exhausting air or other
flue gases.
▶ The condensate trap must be primed at all times.
Failure to do so may allow combustion gases to
escape into boiler room.
▶ External insulation on plastic vent pipe is prohibited.
6720810590-54.1Wo
1
2
3
4
NOTICE:
Vent connectors
▶ Vent connectors serving appliances vented by
natural draft shall not be connected to any portion of
mechanical draft systems operating under positive
pressure.
NOTICE:
Burner damage!
▶ Avoid drawing in combustion air excessively loaded
with dust or airborne particles.
To avoid moisture and frost build-up and to maintain
clearances to openings on adjacent homes, 45° and 90°
elbows or tees may be attached to the end of the vent
termination pipe to direct exhaust plumes away from the
adjacent structure. The total allowable vent length,
maximum number of elbows and distance to air intake
restrictions must be adhered to.
Consult local and state codes pertaining to special
building code and fire department requirements. Adhere
to national code requirements.
Observe the listed maximum lengths of vent system,
which are boiler model dependent (
chapter 6.8.3).
X
X
X
X
1
2
6 720 641 933-19.1O
Содержание KBR16-3
Страница 81: ...Spare parts 81 6 720 810 590 2015 05 Greenstar FS Fig 94 Group 1 Sheet metal Greenstar 6720810590 73 1Wo ...
Страница 85: ...Spare parts 85 6 720 810 590 2015 05 Greenstar FS Fig 96 Group 3 Gas valve Greenstar 6720810590 75 1Wo ...
Страница 91: ...Spare parts 91 6 720 810 590 2015 05 Greenstar FS Fig 99 Group 6 Control box Greenstar 6720810590 78 1Wo ...
Страница 98: ...98 Greenstar FS 6 720 810 590 2015 05 Notes ...
Страница 99: ... 99 6 720 810 590 2015 05 Greenstar FS Notes ...