6 720 816 815 (2016/10)
Greentherm 9800 SE 160/199 | SEC 199
56 | Problem solving
Note: If the appliance is locked for safety reasons, information is shown on the display to give more information on the problem.
Once the problem is solved, you may have to touch the ON/OFF button for 3 sec. to restart the appliance.
EF
Wrong gas type.
▶ Natural gas appliance supplied with liquid gas.
▶ Liquid gas appliance supplied with NG.
F2
ECU internal error.
▶ To unlock, reset the appliance by touching the
ON/OFF button for 3 sec.
▶ If the problem persist replace ECU.
F3
Memory failure
▶ To unlock, reset the appliance by touching the
ON/OFF button for 3 sec.
▶ If the problem persist replace ECU.
F7
A flame is detected before gas valve open.
▶ Check the electrodes and the cable.
▶ To unlock, reset the appliance by touching the
ON/OFF button for 3 sec.
▶ If the problem persist replace ECU.
F9
Safety gas solenoid valve disconnected.
▶ Check connections.
▶ To unlock, reset the appliance by touching the
ON/OFF button for 3 sec.
FA
Fault in the main gas shut-off valve or gas manifold
shut-off valve.
▶ Main gas shut-off valve or gas manifold shut-off
valve mechanical stuck/locked.
▶ Check main gas shut-off valve and gas manifold
shut-off valve electric circuit.
FC
Buttons touched for more than 30s.
▶ Release the button.
Display reads
SOLAR
but without
existence of solar
thermal system.
The hot water temperature selected is lower than
the minimum power that the appliance supplies.
▶ Minimum power is 9,000 BTU.
▶ Increase the hot water flow.
▶ increase the setpoint temperature.
Display reads
SOLAR
and water
temperature low.
High pitch noise
Combustion flame with gas in excess or lack of air
(combustion adjustment is rich).
▶ Check gas supply is according appliance gas type
(NG or LP).
▶ Check appliance CO
2
adjustment (excessive CO
2
,
see table 24).
Increase A1 or A2 air adjustment parameter.
Low pitch noise with
vibration
Combustion flame with air in excess or lack of gas
(combustion adjustment is lean).
▶ Check gas supply is according appliance gas type
(NG or LP).
▶ Check gas pressure supply (gas pressure too
low).
▶ Check appliance CO
2
adjustment (low CO
2
, see
table 24).
Decrease A1 or A2 air adjustment parameter.
1) only to be carried out by qualified contractors.
2) see temperature resistance charts in fig. 52 and 53.
Display
Description
Solution
Table 26