6 720 816 815 (2016/10)
Greentherm 9800 SE 160/199 | SEC 199
Problem solving | 55
CA
Air in the water circuit (commissioning).
Water flow above maximum value specified
(
9.24GPM).
▶ Disconnect the appliance and purge hydraulic
circuit.
▶ Install water flow restrictor.
▶ Check water pressure does not exceed 150 psi.
CF
C1
CE
- Vent blockage during operation (Flue vent outlet
or air vent inlet). Insufficient combustion air.
- Air flow insufficient for start-up (Before flame
ignition).
- Flue outlet vent blockage (exhaust pressure
above siphon water column). Excessive flue vent
pressure.
▶ Remove blockage from the exhaust/intake vent.
▶ Check room air inlet requirements. See chapter
▶ Reset the appliance.
C3
Flow sensor does not detect water recirculation.
▶ Check pump and connections.
▶ Check recirculation circuit for any blockage.
E0
Internal failure on ECU.
▶ Reset failure by long press (3sec.) on ON/FF
button.
▶ If the problem persist replace ECU.
E1
Hot water temperature sensor detects overheating
(> 194 °F).
▶ Let the appliance cool down and try again.
▶ Check sensor resistance.
E3
Flue gas temperature sensor detects high
temperature (> 194 °F).
▶ Let the appliance cool down and try again.
▶ Check sensor resistance.
E4
Temperature inside the cabinet is above 194 °F.
▶ Check for flue gas leakage inside the cabinet.
▶ Let the appliance cool down and try again.
▶ Check sensor resistance.
E5
Copper heat exchanger gas temperature sensor
detects temperature above 392 °F, the appliance
is locked.
E7
Internal error
▶ To unlock, reset the appliance by touching the
ON/OFF button for 3 sec.
▶ If the problem persist replace ECU.
E8
Error during ionization test. ECU internal error.
▶ ECU may need to be replaced.
E9
Thermofuse open.
Temperature above 237 °F.
▶ Replace thermofuse cable.
EA
Flame not detected.
Ionization loss 9 consecutive times.
▶ Check the gas supply pressure.
▶ To unlock, reset the appliance by touching the
ON/OFF button for 3 sec.
▶ If the problem persist check the ignition electrode
or the ionization electrode.
▶ Check Air/Gas flow adjustment.
EC
Partial ionization loss 5 times.
▶ Check the gas supply pressure.
▶ To unlock, reset the appliance by touching the
ON/OFF button for 3 sec.
▶ If the problem persist check the ignition electrode
or the ionization electrode.
EE
Modulating gas solenoid valve disconnected.
▶ Check valve connection.
Display
Description
Solution
Table 26
Содержание Greentherm 9800 SE 160/199