22 | Installation instructions
Required other than direct vent terminal clearances (single pipe penetration)
Fig. 11
[*]
For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA-B149.1, one of the following shall be indicated:
a) a minimum clearance value determined by testing in accordance with Clause 5.20, Draft hoods, or;
b) a reference to the following footnote:
“Clearance in accordance with local installation codes and the requirements of the gas supplier.”
Canadian installations
1)
with
non direct vent terminals
U.S. installations
2)
with non
direct vent terminals
A
Clearance above grade, veranda, porch, deck or balcony.
12 in. (30cm)
12 in. (30cm)
B
Clearance to window or door that may be opened.
36 in. (91cm)
48 in. (1.2 m) below or to side of
opening; 12 in. (30cm) above
opening)
C
Clearance to permanently closed window
*
*
D
Vertical clearance to ventilated soffit located above the terminal within a
horizontal distance of 2 feet (61cm) from the center line of the terminal
*
*
E
Clearance to unventilated soffit
*
*
F
Clearance to outside corner
*
*
G
Clearance to inside corner
*
*
H
Clearance to each side of center line extended above meter/regulator
assembly
36 in. (91cm) within a height
15 ft (4.6m) above the meter/
regulator assembly
*
I
Clearance to service regulator vent outlet
36 in. (91cm)
*
J
Clearance to nonmechanical air supply inlet to building or the combustion
air inlet to any other appliance
36 in. (91cm)
48 in. (1.2m) below or to side of
opening; 1 ft (300mm) above
opening
K
Clearance to mechanical air supply inlet
6 ft (1.83 m)
36 in. (91cm) above if within 10
ft (3m) horizontally
L
Clearance above paved sidewalk or paved driveway located on public
property
7 ft (2.13m)
3)
*
M
Clearance under veranda, porch deck or balcony
12 in (30cm)
4)
*
Table 10
1)
In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2)
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
3) A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both
dwellings.
4) Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.