6 720 816 815 (2016/10)
Greentherm 9800 SE 160/199 | SEC 199
Troubleshooting | 53
▶ Touch the symbol
.
▶ Close water taps.
8.9.4 Returning to Service
▶ Remove the CO
2
analyzer probe and insert the screw into
the flue adaptor.
▶ Touch the symbol
to return to main menu.
The appliance is ready for normal operation.
Readings Gas parameter
Air Adjustment
Max.
Power
L1 value:_____
A1 value:_____ CO
2
value:_____
Min.
Power
L2 value:_____
A2 value:_____ CO
2
value:_____
Table 23
CO
2
range (%)
Max. CO level
(measured)
Greentherm 9800 SE / SEC
199 000 BTU
Nat. Gas
max. input
P1
8.4 % - 8.8 %
< 250 ppm
min. input
P2
2.5 % - 2.7 %
< 30 ppm
LP Gas
max. input
P1
9.9 % - 10.3 %
< 250 ppm
min. input
P2
2.9 % - 3.1 %
< 30 ppm
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact
CO and CO
2
values. Changes in these inputs can result in
different CO and CO
2
values on the same appliance.
Table 24 CO
2
& CO target numbers
CO
2
range (%)
Max. CO level
(measured)
Greentherm 9800 SE
160 000 BTU
Nat. Gas
max. input
P1
8.7 % - 9.1 %
< 250 ppm
min. input
P2
3.4 % - 3.6 %
< 30 ppm
LP Gas
max. input
P1
10.1 % - 10.5 %
< 250 ppm
min. input
P2
3.8 % - 4.0 %
< 30 ppm
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact
CO and CO
2
values. Changes in these inputs can result in
different CO and CO
2
values on the same appliance.
Table 25 CO
2
& CO target numbers