Applications Manual Bosch Geothermal Heat Pumps
| 97
Bosch Thermotechnology Corp.
Data subject to change
Fig. 115 Flush cart step 5
After this system pressurization, always loosen any
plug at the ends of the loop pump motor(s) to allow
any trapped air to be discharged and to insure the
motor housing has been ooded (not required for
“Taco” circulators).
Always insure that the ow center provides adequate
ow through the Bosch geothermal heat pump by
checking the pressure drop across the heat exchanger
and comparing it to the pressure drop tables in the
Installation and Maintenance Manual for the particular
Bosch geothermal heat pump.