Applications Manual Bosch Geothermal Heat Pumps
| 21
Bosch Thermotechnology Corp.
Data subject to change
4.6.1 Equipment Selection Examples
A Bosch water-to-air geothermal heat pump is never
dependent upon outdoor air temperature as an air-source
heat pump, only the ground temperature, associated
groundwater temperature and soil conditions (for close-
loop applications). First, we will examine equipment
selection for a heating dominant climate utilizing two
different size Bosch geothermal heat pumps, then
equipment selection for a cooling dominant climate
utilizing two different size Bosch geothermal heat pumps.
Example 1:
Following the recommended industry criteria of selecting
the equipment to meet the cooling load calculation, we
rst examine the Bosch three (3) ton geothermal heat
pump as the possible choice for this application, and the
associated Bosch data (Table 3). As a the Bosch two (2)
ton geothermal heat pump is too small, we must examine
the next size up, the Bosch three (3) ton geothermal heat
pump.
Capacity Data - Full Load Cooling - all performance at 1200 CFM and 9.0 GPM
Entering
Fluid Temp.
(F)
Entering
Air Temp.
(F)
Total
Capacity
(MBtuH)
Sensible
Capacity
(MBtuH)
Sensible
to Total
Ratio
Power
Input
(kW)
Heat of
Reject
(MBtuH)
EER
50
70db
61wb
36.10 23.53
0.65
1.67
41.81
21.6
60
34.64
22.76
0.66
1.86
41.00
18.6
70
33.18
22.08
0.67
2.05
40.19
16.2
85
30.99
21.16
0.68
2.34
38.97
13.3
100
28.80
20.36
0.71
2.62
37.75
11.0
50
75db
63wb
38.68
28.14
0.73
1.68
44.43
23.0
60
37.12
27.23
0.73
1.87
43.52
19.8
70
35.56
26.41
0.74
2.06
42.61
17.2
85
33.22
25.33
0.76
2.35
41.24
14.1
100
30.87
24.37
0.79
2.64
39.87
11.7
50
80db
67wb
42.47
31.08
0.73
1.70
48.26
25.0
60
40.75
30.08
0.74
1.89
47.20
21.6
70
39.04
29.17
0.75
2.08
46.14
18.8
85
36.47
27.98
0.77
2.37
44.56
15.4
100
33.91
26.92
0.79
2.66
42.97
12.8
50
85db
71wb
46.25
34.05
0.74
1.71
52.08
27.1
60
44.39
32.95
0.74
1.90
50.88
23.3
70
42.52
31.96
0.75
2.10
49.68
20.3
85
39.73
30.65
0.77
2.39
47.88
16.6
100
36.94 29.49
0.80
2.68
46.08
13.8
Tab. 3
(EFT Range (Standard) 50F to 100F)
Example 1:
f
Heating Dominate Climate
f
Minneapolis, Minnesota
[typical entering fluid
temperature (EFT) of 47°F]
f
Load Calculation Sensible Heat Loss
= 65,000 Btu/h
(outdoor design temperature = -12°F; indoor design
temperature = 70°F)
f
Load Calculation Sensible Heat Gain
= 24,000 Btu/h
(outdoor design temperature = 89°F; indoor
temperature = 75°F)
f
Load Calculation Latent Heat Gain
= 8,000 Btu/h
f
Total Heat Gain (Sensible plus Latent)
= 32,000 Btu/h
(slightly larger than a 2-½ ton unit)
f
Per Manual S, 25% larger than the total cooling load
= 1.25 x 32,000 Btu/h = 40,000 Btu/h
f
Maximum Bosch water-to-air geothermal heat pump
size
= 3.3 tons (40,000 Btu/h Cooling Capacity)
Unit selected:
Bosch three (3) ton
Содержание Geothermal Heat Pumps
Страница 1: ...Bosch Geothermal Heat Pumps For Residential Applications Applications Manual ...
Страница 2: ...2 Bosch Geothermal Heat Pumps Bosch Thermotechnology Corp Data subject to change Applications Manual ...
Страница 126: ...126 Bosch Geothermal Heat Pumps Bosch Thermotechnology Corp Data subject to change Applications Manual ...
Страница 127: ...Applications Manual Bosch Geothermal Heat Pumps 127 Bosch Thermotechnology Corp Data subject to change ...